Introduction
Selecting fused circuit protection
The following fuse selection tables are based on the 2017 NEC and
provide fuse recommendations for the listed applications.
These are only suggestions. Final fuse selection should be
performed by qualified personnel able to fully assess an application's
circuit protection requirements.
If you need assistance in selecting a fuse, contact the Eaton
Application Engineering team Monday through Friday, 7:00 a.m. —
5:00 p.m. Central time.
Application Engineering can be reached via phone (toll-free 855-287-
7626 ) and email (FuseTech@Eaton.com).
To locate the recommended fuse product pages, use the index
starting on page 16-4.
Ballasts
Location
Type
Notes
Fuse recommendation
Fuse holder recommendation
Indoor
Fluorescent
Consult fixture manufacturer for size
and type
GLR, GMF, GRF
HLR
GLQ, GMQ
HLQ
All other (mercury,
sodium, etc.)
Consult fixture manufacturer for size
and type
BAF, KTK, FNM, FNQ
HPF, HPS
KTK-R, FNQ-R, LP-CC
HPS-RR, HPF-RR
BBS
HPS-L, HPF-L
SC up to 15 amps
HPF-EE, HPS-EE
SC 20 amp
HPF-JJ, HPS-JJ
SC 25-30 amps
HPF-FF, HPS-FF
Outdoor
Mercury, sodium, etc.
Consult fixture manufacturer for size
and type.
BAF, KTK, FNM, FNQ
HEB, HEX, HPC-D
KTK-R, FNQ-R, LP-CC
HEY, HEZ
Capacitors (NEC 460)
Protected by
Sizing
Fuse/volt recommendation
Time-delay fuses
150% to 175% of Full Load Current (FLC)
Up to 250 V: LPN-RK_SP, FRN-R
Up to 600 V: LPS-RK_SP, FRS-R, LPJ_SP, LP-CC, FNQ-R, TCF
Non time-delay fuses
250% to 300% of Full Load Current (FLC)
Up to 250 V: KTN-R
Up to 300 V: JJN
Up to 600 V: KTS-R, JKS, KTK-R, JJS, FCF_RN
On loadside of motor
running overcurrent
device
Protection recommended as shown, but not required
Electric heat (NEC 424)
Heating type
Sizing
Fuse/volt recommendation
Space heating
125% or next size larger but in no case larger than 60
amps for each subdivided load
Up to 250 V: LPN-RK_SP, FRN-R, NON
Up to 300 V: JJN
Up to 480 V; SC 25 to SC 60
Up to 600 V: LPS-RK_SP, FRS-R, NOS, JJS, LPJ_SP, LP-CC,
FNQ-R, JKS, KTK-R, TCF, SC 1/2 to SC 20, FCF_RN
Boilers (ASME
rated and stamped
vessel)
125% or next size larger but in no case larger than 150
amps for each subdivided load
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
ii
Introduction
Mains, feeders, branches (NEC 430)
Circuit type
Circuit loads
Sizing
Fuse/volt recommendation
Feeder circuits
600 A
No motor load
100% of non-continuous load plus 125% of continuous load
Up to 250 V: LPN-RK_SP, FRN-R
Up to 300V: JJN
Up to 600 V: LPS-RK_SP, FRS-R, JJS,
LPJ_SP, LP-CC, JKS, KTK-R
Combination motor
and other loads
150% of the FLA of largest motor (if there are two or more
motors of same size, one is considered to be the largest)
plus the sum of all the FLA for all other motors plus 100% of
non-continuous, non-motor load plus 125% of continuous, non-
motor load. A maximum of 175% (or the next standard size if
175% does not correspond to a standard size) is allowed for all
but wound rotor and all DC motors.
Up to 250 V: LPN-RK_SP, FRN-R
Up to 600 V: LPS-RK_SP, FRS-R,
LPJ- SP, LP-CC
Motor loads
150% of the FLA of largest motor (if there are two or more
motors of same size, one is considered to be the largest) plus
the sum of all the FLA for all other motors. A maximum of
175% (or the next standard size if 175% does not correspond
to a standard size) is allowed for all but wound rotor and all DC
motors.
Main, branch
and feeder
circuits
(601-6000 A)
150% to 225% of full load current of largest motor plus 100%
of full load current of all other motors plus 125% of continuous
non-motor load plus 100% of non-continuous non-motor load
Up to 600 V: KRP-C_SP
Motor loads (NEC 430)
Circuit voltage
Fuse type
Fuse sized for
Sizing
Fuse/volt recommendation
600 V and less
Time-delay
fuses
Backup overload with
motor starter and short-
circuit protection
125% of motor FLA or next size larger
Up to 250 V: FRN-R
Up to 600 V: FRS-R
130% of motor FLA or next size larger
Up to 250 V: LPN-RK_SP
Up to 600 V: LPS-RK_SP
Short-circuit only
175% of motor FLA or next size larger. (If
175% does not correspond to a standard
size). If this will not allow motor to start,
due to higher than normal inrush currents
or longer than normal acceleration times (5
seconds or greater), fuse may be sized up to
225% or next size smaller.
NOTE
: 150% for
wound rotor and all DC motors.
Up to 250 V: LPN-RK_SP, FRN-R
Up to 600 V: LPS-RK_SP, FRS-R,
LPJ_SP, TCF
Non-time delay
and all Class
CC fuses
Short-circuit only
Maximum of 300% of motor FLA or next
size larger (if 300% does not correspond to
a standard size). If this will not allow motor
to start due to higher than normal inrush
currents or longer than normal acceleration
times (5 seconds or greater), fuses through
600 amps may be sized up to 400% or next
size smaller.
Note
: 150% for wound rotor
and all DC motors.
Up to 250 V: KTN-R
Up to 300 V: JJN
Up to 600 V: KTS-R, JJS, LP-CC, JKS,
KTK-R, FCF_RN
Above 600 V
Compare the minimum melting time-current
characteristics of the fuses with the time-
current characteristics of the overload relay
curve. The size fuse which is selected
should be such that short-circuit protection
is provided by the fuse and overload
protection is provided by the controller
overload relays.
Up to 2400 V: JCH, JCK, JCK-A,
JCK-B, 2ACLS, 2BCLS, 2CLS, 2HCLS
Up to 4800 V: JCL, JCL-A, JCL-B,
5ACLS, 5BCLS, 5CLS, 5HCLS
Up to 7200 V: 7BCLS, 7.2WKMSJ,
8ACLS, 8CLS
Solenoids (coils)
Fuse type
Sizing
Fuse/volt recommendation
Branch circuit
Size at 125% or next size smaller
Up to 250 V: LPN-RK_SP, FRN-R (best)
Up to 600 V: LPS-RK_SP, FRS-R, LPJ_SP, LP-CC, FNQ-R, TCF
Supplemental
Size at 125% or next size larger
Up to 32 V: MDL 9-30 A, FNM 20-30 A
Up to 125 V: MDA 25-30 A, FNM 12-15 A
Up to 250 V: MDL 1/16-8 A, MDA 2/10-20 A, FNM 1/10-10 A, MDQ 1/100-7 A
Up to 500 V: FNQ 1/10-30 A
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
iii
Introduction
Transformers 600 V nominal or less (NEC 450.3)
Protection type
Thermal
overload
protection
Transformer
impedance
Rated
current
Optimum
protection*
NEC maximums
Fuse/volt recommendation
Primary
only (Note:
components on
the secondary
still need
overcurrent
protection)
Primary
< 2 amps
125% or next
size larger
300% or next size smaller (see
NEC 430.72(C) for control circuit
transformer maximum of 500%)
Up to 250 V: LPN-RK_SP,
FRN-R
Up to 600 V: KRP-C_SP,
LPJ_SP, LPS-RK_SP, FNQ-R,
FRS-R, TCF
Primary
2 amps
but < 9
amps
125% or next
size larger
167% or next size smaller
Primary
9 amps
125% or next
size larger
125% or next size larger**
Primary and
secondary
Without
Secondary
< 9 amps
(see
A
)
Primary and
secondary
fuses at 125%
of primary and
secondary FLA
or next size
larger
% of primary FLA (or next FLA
size smaller)
A
= 250%
B
= 250%
C
= 600%
D
= 600%
E
= 400%
F
= 400%
% of secondary FLA
A
= 167% or next size smaller
B
= 125% or next size larger**
C
= 167% or next size smaller
D
= 125% or next size larger**
E
= 167% or next size smaller
F
= 125% or next size larger**
Secondary
9 amps
(see
B
)
With
6%
Secondary
< 9 amps
(see
C
)
Secondary
9 amps
(see
D
)
> 6% but
< 10%
Secondary
< 9 amps
(see
E
)
Secondary
9 amps
(see
F
)
*
When sizing the primary fuse for optimum protection, verify the inrush current with the transformer manufacturer and review fuse time-current characteristics.
**
When 125% of FLA corresponds to a standard rating, the next larger size is not permitted.
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
iv
Introduction
Transformers over 600 V nominal (NEC 450.3)
Supervised installations
Protection for
Transformer
impedance
Primary Sizing
Secondary
volts
Secondary sizing Fuse/volt recommendation
Primary only
N/A
Code maximum of 250%
or next standard size if
250% does not correspond
to a standard rating
Note: Components on
the secondary still need
overcurrent protection
N/A
N/A
Up to 250 V: LPN-RK_SP, FRN-R
Up to 600 V: LPS-RK_SP, LPJ-_SP, KRP-C_SP,
FRS-R, FNQ-R, TCF
Up to 2.475 kV: 2NCLPT, 2CLPT
Up to 2.75 kV: 2CLE, 2HLE
Up to 2750/5500 V: JCW
Up to 5.5 kV: 5HLE, 5CLE, 5HCL, 5BHCL,
5BHLE, 5AHLE, JCY, MV05, 5.5 ABWNA, 5.5
AMWNA, 5.5 FFN
7 Up to 7.2 kV:.2 AMWNA, 7.2 TDLSJ, 7.2
TFLSJ
Up to 8.3 kV: 8HLE, 8CLE, 8BHLE, 8AHLE,
8CLPT, 8NCLPT, 8HCL, 8.25 FFN
Up to 15.5 kV: 15CLPT, 15NCLPT, 15CLE,
15HLE, 15BHLE, 15LHLE, 15HCL, 15BHCL,
MV155, 15.5 CAVH
Up to 17.5 kV: 17.5 CAV, 17.5 TDM
Up to 24 kV: 24 TDM, 24 TFM, 24 FFM
Up to 36 kV: 36 CAV, 36 TDQ, 36 TFQ
Up to 38 kV: 38CLPT, 38 CAV
Primary and
secondary
6%
At code maximum of 300%
> 600 V
At code maximum
of 250%
600 V
At code maximum
of 250%
> 6% but
< 10%
At code maximum of 300%
> 600 V
At code maximum
of 225%
600 V
At code maximum
of 250%
Unsupervised installations
Transformer
impedance
Primary Sizing
Secondary
volts
Secondary sizing
Fuse/volts recommendation
6%
At code
maximum of
300% or next
standard size if
300% does not
correspond to a
standard rating
> 600 V
At code maximum of 250% or
next standard size if 250% does
not correspond to a standard
rating
Up to 250 V: LPN-RK_SP, FRN-R
Up to 600 V: LPS-RK_SP, LPJ-_SP, KRP-C_SP, FRS-R,
FNQ-R, TCF
Up to 2475 V: 2NCLPT, 2CLPT
Up to 2.75 kV: 2CLE, 2HLE
Up to 2750/5500 V: JCW
Up to 5.5 kV: 5HLE, 5CLE, 5HCL, 5BHCL, 5BHLE,
5AHLE, JCY, MV05, 5.5 ABWNA, 5.5 AMWNA, 5.5 FFN
Up to 7.2 kV: 7.2 AMWNA, 7.2 TDLSJ, 7.2 TFLSJ
Up to 8.3 kV: 8HLE, 8CLE, 8BHLE, 8AHLE, 8CLPT,
8NCLPT, 8HCL, 8.25 FFN
Up to 15.5 kV: 15CLPT, 15NCLPT, 15CLE, 15HLE,
15BHLE, 15LHLE, 15HCL, 15BHCL, MV155, 15.5 CAVH
Up to 17.5 kV: 17.5 CAV, 17.5 TDM
Up to 24 kV: 24 TDM, 24 TFM, 24 FFM
Up to 36 kV: 36 CAV, 36 TDQ, 36 TFQ
Up to 38 kV: 38CLPT, 38 CAV
600 V
At code maximum of 125% or
next standard size if 125% does
not correspond to a standard
rating
> 6% but < 10%
At code
maximum of
300% or next
standard size if
300% does not
correspond to a
standard rating
> 600 V
At code maximum of 225% or
next standard size if 225% does
not correspond to a standard
rating
600 V
At code maximum of 125% or
next standard size if 125% does
not correspond to a standard
rating
Solid state devices (diodes, SCRs, triacs, transistors)
Protection type
Sizing
Fuse/volts recommendation
Short-circuit only
F, S, K, and 170M fuse families sized up to several sizes
larger than full load RMS or DC rating of device
Up to 130 V: FWA
Up to 250 V: FWX
Up to 500 V: FWH
Up to 600 V: FWC, KAC, KBC
Up to 700 V: FWP, 170M_, SPP
Up to 1000 V: FWJ, 170M_, SPJ
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
v
【选型】Eaton Bussmann(伊顿巴斯曼) 电路保护熔断器(保险丝)选型指南
选型目录:
Fuse Protection Upgrading Introduction
Fused Circuit Protection Selection Advice
Low Voltage Branch Circuit Fuses
Low Voltage Supplemental Fuses and Limiters
Electronic/PCB/Small Dimension Fuses
High Speed Fuses
IEC and British Standard Fuses
Photovoltaic Fuses/Fuses Holders/Fuses Blocks
Medium Voltage Fuses
Fuse Blocks and Holders
Power Distribution and Terminal Blocks
Connector Products
Disconnect Switches
Quik-Spec Electrical Gear
Surge Protective Devices
Telecom Protection Products
Fuse&Fuse Block Accessories
Fuse&Fuse Block Cross Reference and Index
Low-Peak Upgrade Program and Fuse Inventory Consolidation

您正在使用的浏览器版本过低,将不能正常浏览产品选型内容。

  • 收藏
平台客服
服务热线

联系我们

954668/400-830-1766(工作日 9:00-18:00)

service@sekorm.com

投诉与建议

E-mail:claim@sekorm.com

商务合作

E-mail:contact@sekorm.com

收藏
收藏当前页面