Eaton Bussmann Quik-Spec™ Electrical Gear Selection Guide
【选型】Eaton Bussmann(伊顿巴斯曼) 电路保护熔断器(保险丝)选型指南
选型目录:
Fuse Protection Upgrading Introduction
Fused Circuit Protection Selection Advice
Low Voltage Branch Circuit Fuses
Low Voltage Supplemental Fuses and Limiters
Electronic/PCB/Small Dimension Fuses
High Speed Fuses
IEC and British Standard Fuses
Photovoltaic Fuses/Fuses Holders/Fuses Blocks
Medium Voltage Fuses
Fuse Blocks and Holders
Power Distribution and Terminal Blocks
Connector Products
Disconnect Switches
Quik-Spec Electrical Gear
Surge Protective Devices
Telecom Protection Products
Fuse&Fuse Block Accessories
Fuse&Fuse Block Cross Reference and Index
Low-Peak Upgrade Program and Fuse Inventory Consolidation
Quik-Spec™ electrical gear —
12
Quik-Spec
Electrical gear
Contents
Description
Section
page
Quik-Spec™ Coordination Panelboards
QSCP Up to 400 A
2
QSCP 600 to 1200 A
3
Quik-Spec elevator disconnects
Power Module™ switches and panels
4-5
HVAC disconnects
Fused, non-fused, GFCI
6
Bussm
ann se
ries Qu
ik-Spec
TM
Co
ordination Pa
ne
lbo
ard
Up to 20
0 kA SC
CR in 40% less
space than
traditional
solution
s
Plu
s, the
ea
siest way to ac
hie
ve
select
ive
coordination
12-1
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
12
— Quik-Spec™ electrical gear
30-400A Quik-Spec™ Coordination Panelboard (QSCP)
Configurable 600 Vac fused panelboard with from 30 to 400 amp
mains, 15 to 100 amp 1-, 2- and 3-pole branch switches and 18,
30 or 42 branch circuit positions. Finger-safe fused branch circuit
switches use the time-delay or fast-acting CUBEFuse available in
ratings from 1 to 100 amps.
Ratings
•
Volts
•
Up to 600 Vac
•
Up to 125 Vdc *
•
Amps
30, 60, 100, 200, 225 or 400 A
•
SCCR
•
200 kA, 100 kA or 50 kA AC
•
100 kA or 20 kA@125 Vdc*
*
Vdc rating applicable to MLO panels only. 50 and 60 amp switches are rated 125
Vdc for installed fuse amp ratings up to 40 A and 24 Vdc for installed fuse amp
ratings from 45 to 60 A. 90 and 100 amp switches are rated 125 Vdc for installed
fuse amp ratings up to 80 A and 24 Vdc for installed fuse amp ratings from 90 to
100 A.
Agency information
•
UL Listed to UL 67
•
Complies with NFPA 70
Mains
•
MLO (main lug only)
•
Fused disconnect
•
Non-fused disconnect
Enclosure**
•
NEMA 1 (top or bottom feed)
•
NEMA 3R (bottom feed only)
•
Consult factory for other ratings
**
Standard size 20" W x 5" D x various heights, depending on configuration. Flush
mount and door-in-door not available with NEMA 3R enclosure.
Mounting
•
Surface – NEMA 1 and 3R
•
Flush – NEMA 1 only
Doors
•
Single - NEMA 1 and 3R
•
Door-in-Door – NEMA 1 only
Branch positions
•
18, 30 and 42 (factory configured)
Branch switches
•
1-, 2- and 3-pole amp rating rejecting CCP2B fused switches
†
(field
installable)
•
Amp rejection breaks 15, 20, 30, 40, 50, 60, 70, 90, 100 A
†
CCP2Bs will not accept a fuse with a greater amp rating than the switch.
Data sheet no. 1160
CCP2B 3-pole branch
switch features lockout
provision for 1/4" lock
Loadside lugs and disconnect
•
Feed-through single and double
•
Fused loadside disconnect,
≥
100 to
≤
200 amp (400 amp panels
only)
Neutrals
•
200, 400 and 800 A unbonded and bonded
Ground
•
Non-isolated or isolated
Features
•
UL Listed and cULus to Canadian Standard 22.2, No. 29-M1989
make it easy to address NEC and CEC selective coordination
requirements in an all fused system or upstream Eaton circuit
breakers
•
Value-engineered for greater flexibility with up to 400 amp mains,
200 kA SCCR, 100 A branches with 18, 30 and 42 branch positions
•
Same size footprint as traditional circuit breaker panelboards and
40% smaller than standard fusible panelboards: 20" W x 5-3/4" D x
various heights (depending on configuration)
•
Increased safety with the current-limiting finger-safe Class CF
CUBEFuse that helps reduce arc flash hazard levels
Optional surge protection
2017 NEC 700.8 requires a listed SPD to be installed in or on all
emergency system panelboards.
Any QSCP intended for installation on an AC circuit can be ordered
with an Surge Protective Device to comply with NEC 700.8.
The installed SPDs feature a remote Form C contact relay (rated at
250 Vac/0.5 A ) for easy integration into a monitoring system.
Ordering
The QSCP is factory configured to the specific electrical system. To
place your order, contact your Bussmann series product distributor
or representative and provide the relevant electrical and circuit
information for your installation.
12-2
BUSSMANN SERIES FULL LINE C
ATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
Quik-Spec™ electrical gear —
12
Quik-Spec
Electrical gear
600-1200A Quik-Spec Coordination Panelboard (QSCP)
Data sheet no. 1171
Configurable fused panelboard with 600, 800 and 1200 amp MLO
mains and branch switches up to 600 amps.
Ratings
•
Volts
•
Up to 600 Vac
•
Up to 125 Vdc
•
Amps 600, 800, 1200 A
•
SCCR 200 kA
Agency information
•
UL Listed to UL 67
•
Complies with NFPA 70
Assembly
•
Main lug only
•
Floor mount NEMA 1 enclosure
•
Branch switches 1-, 2- and 3-pole, 15 to 600 A
Available branch switch fuses
•
Fast-acting or time-delay Class J (time-delay LPJ or fast-acting
JKS) non-CCP2B disconnects only
•
High speed DFJ Class J fuses (non-CCPB disconnects only)
•
Fast-acting or time-delay Class CF (time-delay TCF or fast-acting
FCF) CCP2B disconnects only
Features
•
Configurable panelboards with options for 600, 800 and 1200 A
MLO mains and branches from 15-600 A all rated 200 kA SCCR at
600 Vac
•
The CCP2B finger-safe branch switches (utilizing the UL Class
CF CUBEFuse up to 100 A) features amp rating rejection to help
prevent overfusing
•
Fused switches make it simple to address NEC selective
coordination system requirements in an all fused system or qwith
upstream Eaton circuit breakers.
Ordering
The QSCP is factory configured to the specific electrical system. To
place your order, contact your Bussmann series product distributor
or representative and provide the relevant electrical and circuit
information for your installation.
Configuration and dimensions — in
Panel
amps
Branch configurations
H
W
D
600
(18) 1-100 A
65
27
15
(18) 1-100 A + 200 A single
(18) 1-100 A + 200 A twin
200 A single + 200 A single
200 A single + 200 A twin
200 A twin + 200 A twin
(2) 300 A single
89
38
15
800
(18) 1-100 A + 200 A single
65
38
15
(18) 1-100 A + 200 A twin
(2) 200 A twin
(18) 1-100 A + 400 A single
89
38
15
200 A twin + 400 A single
(2) 400 A single
1200
(18) 1-100 A + 600 A single
89
38
15
(3) 200 A twin
200 A twin + 600 A single
(2) 200 A twin + 400 A single
(3) 400 A single
102
38
15
600 A single + 400 A single + 200 A single
600 A single + 400 A single + 200 A twin
(2) 600 A single
12-3
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
12
— Quik-Spec™ electrical gear
Quik-Spec Power Module switch and panel
all-in-one elevator disconnects
Fused power switch (PS) or panel (PMP) with shunt trip and fire
safety interface provide a single point tie in with fire alarm systems.
Ratings
•
Volts 600 Vac, 3Ø
•
Amps*
•
30-400 A (PS)
•
30-200 A (PMP feeder switches)
•
400-800 A (PMP main switches)
•
SCCR 200 kA RMS
*
Contact your Bussmann series product representative for applications greater
than 800 amps.
Agency information
•
Power Module switch (
PS
) —
UL Listed (UL 98) enclosed and
dead front switch Guide 96NK3917, File E182262, NEMA 1, UL
50 Listed enclosure**, cUL per Canadian Standards C22.2, No.
0-M91-CAN/CSA C22.2, No. 4-M89 Enclosed switch.
•
Power Module Panel (
PMP
) —
UL 98 enclosed and deadfront
switches, complies with NFPA 70
**
NEMA 12, 3R, and 4 enclosures also available.
Elevator shutdown
•
ANSI/ASME A17.1, 2.8.3.3.2
•
NEC 620.51(B) (elevator shutdown)
•
NEC 240.12 (orderly shutdown)
•
Shunt trip voltage monitoring
•
NFPA 72, 6.16.4.4
Selective coordination
•
NEC 620.62
Auxiliary contact (hydraulic elevator)
•
NEC 620.91(C)
Features
•
Internally powered, relay activated shunt trip system
•
Mechanically interlocked auxiliary contact
•
Self-contained adherence to elevator consensus standards, NFPA
70, NFPA 72, ANSI/ASME A17.1
•
Shunt trip capability
•
Fire safety signal interface
•
Shunt trip voltage monitoring
•
Component protection with Low-Peak™ Class J fuses
•
Lockable in the open position with three-lock capability
•
Optional key-test switch and optional pilot light for easy inspection
•
No annual calibration or testing of overcurrent protection required
•
Padlockable for service-work safety and open-door “override” for
troubleshooting
Data sheet no. 1145 (switch) 1146 (panel)
PS
†
Power Module Switch for single elevator applications.
PMP
†
Power Module Panel for multiple elevator applications.
†
Fused main disconnect requires Class J fuses, not supplied with switch.
Typical applications
•
Elevator disconnects
•
Computer room shunt trip disconnect
•
Fire safety interface relay
Accessories
•
For added safety, use the Bussmann series SAMI™ fuse covers
to improve maintenance personnel protection (OSHA 1910.333,
Paragraph C)
Ordering
•
The Quik-Spec Power Module Switch and Panel are factory
configured. To place your order, have all relevant electrical
and circuit information contact your Bussmann series product
representative.
12-4
BUSSMANN SERIES FULL LINE C
ATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
Quik-Spec™ electrical gear —
12
Quik-Spec
Electrical gear
Data sheet no. 1145 (switch) 1146 (panel)
Hydraulic elevators
Hydraulic elevators need battery backup to help prevent stranding
passengers. To keep the elevator from moving when it’s been
manually shut down for maintenance, the NEC requires battery
backup be connected to the elevator disconnecting means through
an auxiliary contact.
However, an unintended consequence can be passengers getting
stranded because of devices that open automatically (circuit breakers
and disconnects utilizing a molded case switch with a trailing fuse
block) will operate with a fault on their loadside. That operation also
disables the battery backup and strands passengers. That’s why the
Power Module has a non-automatic fusible shunt trip switch. If the
Power Module has a fault on its loadside, the fuses open and the
battery stays enabled. Thus the Power Module ensures that battery
power is enabled when the passengers need it to exit - and disabled
to allow safe maintenance of the elevator and hoistway.
Scenario
Battery
lowering
required
Reason
Offered
by
Power
Module
Offered
by other
elevator
discon-
nects
Power
failure
Ye s
Need to lower elevator
and allow passengers
to exit.
Ye s
Ye s
Fire in
shaft or
machine
room
No
Recall is initiated by
smoke detector and
lowers elevator to a
safe floor. Battery not
needed.
Ye s
Ye s
Disconnect
manually
opened
No
Worker to perform
maintenance. Elevator
must remain stationary
to prevent injury.
Ye s
Ye s
Fault on
loadside of
disconnect
Ye s
Need to lower elevator
and allow passengers
to exit.
Ye s
No
QuikShip service program, 3 days for switches and 10
days for panels!
Ship-direct service within three business days for Power Module
switches (PS_) and 10 business days for Power Module panels
(PMP_).
Power Module switch*
Catalog no.
Amps
Volts
PS6T48R1KGBF3-X
60
480
PS1T48R1KGBF3-X
10 0
480
PS1T20R1KGBF3-X
10 0
208
PS2T48R1KGBF3-X
200
480
PS2T20R1KGBF3-X
200
208
Power Module panel**
Catalog no.
Amps
PMP-400-X
400
PMP-600-X
600
PMP-800-X
800
*
Three day PS_ shipment requires ordering from catalog numbers shown,
limit three units or less per order
.
**
10 day PMP_ shipment covers NEMA 1 enclosures with the amp ratings
shown and all requirements for relay type (AC or DC), accessory options and
number of switches. To order PMP_, contact your Bussmann series product
representative with all relevant electrical and circuit information.
Power Module Switch catalog number system
To order, use this build-a-code to specify your Power Module switch.
PS 1 T48 R1 K G N1 B F1 U
PS = Power
Module Switch
Amp rating
†
•
3 = 30, 6 = 60, 1 = 100
2 = 200, 4 = 400
Control transformer*
†
•
T20 = 208 V, T24 = 240 V
T48 = 480 V, T60 = 600 V
Fire safety interface relay
(3PDT, 10A, 12V)
†
•
R1 = 120 Vac coil,
R2 = 24 Vdc coil
Optional key test switch
•
K = Key
Optional pilot light ON
•
G = Green, R = Red
W = White
Optional neutral lug
††
•
N6 = 30-60 A, N1 = 100 A
N2 = 200 A, N4 = 400 A
Auxiliary contacts
†
•
B = 2 NO/NC
Fire alarm voltage monitoring
relay (to monitor shunt trip
voltage)
•
F1 = Single-pole,
F3 = Three-pole**
Optional NEMA enclosures
(Type 1 standard with no
suffix designation required)
•
U = Type 3R, Y = Type 4,
Z = Type 12
*
100 Va with primary and secondary fusing (120 V secondary).
**
Only for use with R1 option.
†
Required equipment.
††
Neutral lug rating should be equal to or greater than the switch amp rating.
12-5
BUSSMANN SERIES FULL LINE CATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
12
— Quik-Spec™ electrical gear
Enclosure
•
Metallic NEMA 3R housing with weather resistant coating
Dimensions
•
See catalog numbers table
Features
•
AC disconnects meet NEC Code requirements under article 440.14
•
Self-testing GFCI units meet NEC Code requirements under
articles 210.63, 210.8, and 406.8(B)(1)
•
NEMA 3R enclosures withstand outdoor environment
•
Padlockable with two-position pullout handle to lock safety shield
when in the ON position. (Not available on GFCI or 60 A switched
units.) For added safety, pullout handle can be stored in the
compartment in the OFF position
Typical applications
•
Residential, light industrial/commercial AC and heat pump service
•
Spas/whirlpools, swimming pools, pump houses
•
Suitable for use as service entrance equipment with field-installed
ground bar. Order catalog number DPFG
Fused and non-fused AC disconnects
Fused and non-fused pullout
AC disconnects in NEMA 3R
enclosures. Fused versions
are available in 30 and 60 amp
ratings with or without self-
testing GFCI receptacles. Non-
fused versions are available in
60 amp versions with or without
self-testing GFCI receptacles.
Ratings
•
Volts
•
120 Vac single-phase
•
240 Vac split-phase
•
Amps 30 or 60 A
Agency Information
•
UL Listed to UL 1429, cUL
Certified, UL Guide WGEW
Conductors
•
3-14 AWG Cu/Al
Fused disconnect
Non-fused disconnect
with GFCI receptacle
Non-fused disconnect
Catalog no.
Description
Amp
rating
Max Hp rating
Fuse
class
Approximate dimensions (in)
120 V
240 V
Height
Width
Depth
Fused disconnects
B221-30F
Pullout disconnect
30
1. 5
3
H or R
8-3/4
5-3/8
2-7/8
B221-30FGFST
Pullout disconnect with GFCI
13
7-1/2
4-3/4
B221-30FGFWTST
Pullout disconnect with weather-resistant/tamper-
resistant rated GFCI
B222-60F
Pullout disconnect
60
3
10
H or R
8-3/4
5-3/8
2-7/8
B222-60FGFST
Pullout disconnect with GFCI
13
7-1/2
4-3/4
B222-60FGFWTST
Pullout disconnect with weather-resistant/tamper-
resistant rated GFCI
Non-fused disconnects
B222-60NF
Pullout disconnect
60
3
10
*
8-3/4
5-3/8
2-7/8
B222-60NFGFST
Pullout disconnect with GFCI
11-3/4
6-1/2
4-1/2
B222-60NFGFWTST
Pullout disconnect with weather-resistant/tamper-
resistant rated GFCI
B222-60NFNA
Disconnect switch
—
8-3/4
5-3/8
3-5/8
*
Upstream overcurrent protective device (OPCD) not to exceed 60 A.
For a 30 and 60 amp pullout replacement handle, order catalog number 96-3258-4.
Recommended Bussmann series fuses
Fuse class
Catalog symbol
Operation
Available amps
Data sheet no.
H
NON-(amp)
One time, general purpose
Up to 60
1030
R
FRN-R-(amp)
Dual element, time-delay
Up to 60
1019
LPN-RK-(amp)SP (non-indicating)
10 03
LPN-RK-(amp)SPI (indicating
35 to 60
10 03
Data sheet no. 1143
12-6
BUSSMANN SERIES FULL LINE C
ATALOG 1007 — OCTOBER 2018
Eaton.com/bussmannseries
【选型】Eaton Bussmann(伊顿巴斯曼) 电路保护熔断器(保险丝)选型指南
选型目录:
Fuse Protection Upgrading Introduction
Fused Circuit Protection Selection Advice
Low Voltage Branch Circuit Fuses
Low Voltage Supplemental Fuses and Limiters
Electronic/PCB/Small Dimension Fuses
High Speed Fuses
IEC and British Standard Fuses
Photovoltaic Fuses/Fuses Holders/Fuses Blocks
Medium Voltage Fuses
Fuse Blocks and Holders
Power Distribution and Terminal Blocks
Connector Products
Disconnect Switches
Quik-Spec Electrical Gear
Surge Protective Devices
Telecom Protection Products
Fuse&Fuse Block Accessories
Fuse&Fuse Block Cross Reference and Index
Low-Peak Upgrade Program and Fuse Inventory Consolidation
您正在使用的浏览器版本过低,将不能正常浏览产品选型内容。
- 收藏