WAGO 1-Phase Power Supplies Selection Guide
WAGO Power Supplies
选型目录:
Power Supplies Overview
1-Phase Power Supplies
3-Phase Power Supplies
Special Power Supplies
Circuit Protection product
DC/DC Converters
UPS-Charger and Controllers and Capacitive Buffer Modules
Redundancy Modules
Energy Measurement Technology
Potential Distribution Blocks
Accessories and Tools
Indexes
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Nominal voltage (output)
Nominal current (output)
[ADC]
Input, 1-phase
Input, 2-phase
Approvals
DC OK signal/
contact
RS-232 interface
TopBoost
1)
PowerBoost
Efficiency
typ. [%]
Ambient temperature
temperature [°C]
4)
Item Number
Page
EN 60335
cURus 60950
cULus 508
cULus 61010
DNV
ANSI/ISA 12.12.1
ATEX/IEC Ex
5 VDC
5.5
■
■
■
75.0
−25 ... +60
787-1020
71
12 VDC
2.0
■
■
■
■
■
■
82.0
−25 ... +70
787-1601
2)
30
2.0
■
■
80.0
−25 ... +60
787-1701
49
2.0
■
■
■
■
80.0
−25 ... +60
787-1001
72
2.5
■
■
■
■
88.0
−25 ... +70
787-1201
61
4.0
■
■
■
■
■
■
86.0
−25 ... +70
787-1611
2)
31
4.0
■
■
81.0
−25 ... +60
787-1711
50
4.0
■
■
■
■
85.0
−25 ... +60
787-1011
73
5.0
■
■
■
■
89.5
−25 ... +70
787-1211
62
6.0
■
■
■
■
87.0
−25 ... +60
787-1021
74
7.0
■
■
■
■
■
■
86.0
−25 ... +70
787-1621
32
8.0
■
■
84.0
−25 ... +60
787-1721
51
8.0
■
■
■
■
91.5
−25 ... +70
787-1221
63
10.0
■
■
■
■
■
93.8
−25 ... +70
2787-2134
12
15.0
■
■
■
■
95.3
−25 ... +70
2787-2135
13
15.0
■
■
■
■
■
■
90.0
−25 ... +70
787-1631
33
DC 18 V
2.4
■
■
■
83.0
−25 ... +60
787-1017
75
1.25
■
■
■
88.0
−25 ... +70
787-2857
69
24 VDC
0.5
■
■
■
83.0
−25 ... +70
787-1200
64
1.0
■
■
■
■
■
■
86.0
−25 ... +70
787-1602
2)
34
1.25
■
■
■
■
80.0
−20 ... +60
787-1702
52
1.25
■
■
88.0
−25 ... +70
2687-2142
46
1.25
■
■
■
88.0
−20 ... +70
787-2850
70
1.3
■
■
■
■
82.0
−25 ... +60
787-1002
76
1.3
■
■
■
■
87.0
−25 ... +70
787-1202
65
2.0
■
■
■
■
■
■
89.0
−25 ... +70
787-1606
2)
35
2.5
■
■
■
■
■
86.0
−10 ... +70
787-712
55
2.5
■
■
■
■
81.0
−20 ... +60
787-1712
53
2.5
■
■
■
■
88.0
−25 ... +60
787-1012
77
2.5
■
■
■
■
89.0
−25 ... +70
787-1212
66
3.0
■
■
■
■
■
■
87.8
−25 ... +70
787-818
24
3.8
■
■
■
■
■
■
87.0
−25 ... +70
787-1616/000-1000
2)
36
4.0
■
■
■
■
■
■
89.0
−25 ... +70
787-1616
37
4.0
■
■
■
■
88.0
−25 ... +60
787-1022
78
4.2
■
■
■
■
90.0
−25 ... +70
787-1216
67
5.0
■
■
■
■
■
91.5
−25 ... +70
2787-2144
14
5.0
■
■
■
■
■
■
87.8
−25 ... +70
787-822
25
5.0
■
■
■
■
■
■
■
89.0
−25 ... +70
787-1622
38
5.0
■
■
■
■
■
■
■
89.0
−25 ... +70
787-1628
44
5.0
■
■
■
■
■
86.0
−10 ... +60
787-722
56
5.0
■
■
■
■
84.0
−20 ... +60
787-1722
57
5.0
■
■
90.0
−25 ... +70
2687-2144
47
6.0
■
■
■
■
90.0
−25 ... +70
787-1226
68
10.0
■
■
93.0
−25 ... +70
2687-2146
48
10.0
■
■
■
■
■
92.8
−25 ... +70
2787-2146
15
10.0
■
■
■
■
■
■
90.0
−25 ... +70
787-832
25
10.0
■
■
■
■
■
■
91.0
−25 ... +70
787-1632
5)
39
10.0
■
■
■
■
■
■
■
90.0
−25 ... +70
787-1638
45
10.0
■
■
■
■
■
86.0
−10 ... +70
787-732
59
10.0
■
■
■
■
84.0
−20 ... +60
787-1732
58
20.0
■
■
■
■
■
94.0
−25 ... +70
2787-2147
16
20.0
■
■
■
■
■
■
91.0
−25 ... +70
787-834
27
20.0
■
■
■
■
■
■
92.0
−25 ... +70
787-1634
40
20.0
■
■
■
■
90.0
−25 ... +70
787-734
60
40.0
■
■
■
■
■
95.0
−25 ... +70
2787-2448
17
40.0
■
■
■
■
90.0
−25 ... +70
787-736
54
WAGO Power Supplies; 1-Phase
Selection Guide
10
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
■ Yes
Pending
1)
TopBoost enables magnetic tripping of circuit breakers in the output circuit.
2)
NEC Class 2 Power Unit per cURus 1310 or cURus 60950
3)
With uninterruptible power supply (UPS)
4)
Device starts at −40°C, type-tested for 787-8xx, -10xx, -16xx, 2787-2xxx
5)
.../000-070 is optionally available with protective coating
Nominal voltage (output)
Nominal current (output)
[ADC]
Input, 1-phase
Input, 2-phase
Approvals
DC OK signal/
contact
RS-232 interface
TopBoost
1)
PowerBoost
Efficiency
typ. [%]
Ambient temperature
temperature [°C]
4)
Item Number
Page
EN 60335
cURus 60950
cULus 508
cULus 61010
DNV
ANSI/ISA 12.12.1
ATEX/IEC Ex
48 VDC
2.0
■
■
■
■
■
■
86.0
−25 ... +70
787-1623
41
5.0
■
■
■
■
■
95.3
−25 ... +70
2787-2154
18
5.0
■
■
■
■
■
■
91.0
−25 ... +70
787-833
28
5.0
■
■
■
■
■
■
92.0
−25 ... +70
787-1633
42
10.0
■
■
■
■
■
95.3
−25 ... +70
2787-2157
19
10.0
■
■
■
■
■
■
91.0
−25 ... +70
787-835
29
10.0
■
■
■
■
■
■
93.0
−25 ... +70
787-1635
5)
43
11
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
2787 Series
Power supply; Pro 2; 1-phase; 12 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; Communication capability
Power supply; Pro 2; 1-phase; 12 VDC output voltage;
10 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2134
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 1.3 A
Inrush current
≤ 9.6 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 40 ms (230 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
12 ... 14 VDC (adjustable)
Nominal output current I
o nom
10 A (12 VDC)
Nominal output power
120 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 15 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
Communication interface, can be used with WAGO USB
Communication Cable (750-923) or IO-Link Communica
-
tion Module (2789-9080), Modbus RTU Communication
Module (2789-9015) or Modbus TCP Communication
Module (2789-9052)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 1.6 W (no load);
≤ 10 W (230 VAC; nominal load)
Efficiency (typ.)
93.8 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,200,000 h (per IEC 61709)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
35 x 130 x 130 (mm) / 1.378 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 166 mm
Mounting type
DIN-35 rail
Weight
650 g
Environmental requirements
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
12
1
www.wago.com
−
−
−
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Pro 2; 1-phase; 12 VDC output voltage; 15 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Power supply; Pro 2; 1-phase; 12 VDC output voltage;
15 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2135
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 2 A (240 VAC; nominal load)
Inrush current
≤ 12 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 40 ms (230 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Nominal output current I
o nom
15 A (12 VDC)
Nominal output power
180 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 22.5 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 2.3 W (no load);
≤ 14 W (230 VAC; nominal load)
Efficiency (typ.)
95.3 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection
Isolation voltage (sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,200,000 h (per IEC 61709)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
70 x 130 x 130 (mm) / 2.756 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 166 mm
Mounting type
DIN-35 rail
Weight
1000 g
Environmental requirements
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
UL 61010-2-201
13
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Pro 2; 1-phase; 24 VDC output voltage;
5 A output current; TopBoost + PowerBoost; Communi
-
cation capability
Item No.
PU
2787-2144
1
DNV
2787-2144/000-030
1
DNV +
Protective coating
2787-2144/000-070
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Power supply; Pro 2; 1-phase; 24 VDC output voltage; 5 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 1 A (240 VAC; nominal load);
≤ 1.8 A (100 VAC; nominal load)
Inrush current
≤ 9 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 7.5 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Power loss P
l
≤ 1 W (standby); ≤ 2 W (no load);
≤ 10 W (230 VAC; nominal load)
Efficiency (typ.)
93.8 % (230 VAC; 5 A; 25 °C)
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,000,000 h (per IEC 61709)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
35 x 130 x 130 (mm) / 1.378 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 166 mm
Mounting type
DIN-35 rail
Weight
650 g
Environmental requirements
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
14
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Pro 2; 1-phase; 24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Power supply; Pro 2; 1-phase; 24 VDC output voltage;
10 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2146
1
DNV
2787-2146/000-030
1
DNV +
Protective coating
2787-2146/000-070
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 1.2 A (240 VAC; nominal load);
≤ 2.7 A (100 VAC; nominal load)
Inrush current
≤ 11 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 25 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 15 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
Communication interface, can be used with WAGO USB
Communication Cable (750-923) or IO-Link Communica
-
tion Module (2789-9080), Modbus RTU Communication
Module (2789-9015) or Modbus TCP Communication
Module (2789-9052)
Efficiency/power losses
Power loss P
l
≤ 1 W (standby); ≤ 2.2 W (no load);
≤ 12 W (230 VAC; nominal load)
Efficiency (typ.)
95.2 % (230 VAC; 10 A; 25 °C)
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,200,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
−3 %/K (> +55 °C and U
i
< 230 VAC);
−3 %/K (> +60 °C and U
i
≥ 230 VAC)
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
50 x 130 x 130 (mm) / 1.969 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 166 mm
Mounting type
DIN-35 rail
Weight
1385 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
15
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Pro 2; 1-phase; 24 VDC output voltage;
20 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2147
1
DNV
DNV
2787-2147/000-030
1
DNV +
Protective coating
2787-2147/000-070
1
Power supply; Pro 2; 1-phase; 24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 2.2 A (240 VAC; nominal load);
≤ 5.9 A (100 VAC; nominal load)
Inrush current
≤ 12 A (after 1 ms)
Power factor
≥ 0.98 (240 VAC)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 24 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 30 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Power loss P
l
≤ 1.3 W (standby); ≤ 2.6 W (no load);
≤ 24 W (230 VAC; nominal load)
Efficiency (typ.)
95.4 % (230 VAC; 20 A; 25 °C)
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-1 %/V (> +40 °C and U
i
< 100 VAC);
−3 %/K (> +55 °C and U
i
< 230 VAC);
−3 %/K (> +60 °C and U
i
≥ 230 VAC);
−5 %/V (U
o
> 24 VDC)
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
70x 130 x 130 (mm) / 2.756 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 169 mm
Mounting type
DIN-35 rail
Weight
1450 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
16
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Pro 2; 1-phase; 24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; Communication capability; Input voltage range: 200 ... 240 VAC
2787 Series
Power supply; Pro 2; 1-phase; 24 VDC output voltage;
40 A output current; TopBoost + PowerBoost;
Communication capability;
Input voltage range: 200 ... 240 VAC
Item No.
PU
2787-2448
1
DNV
DNV
2787-2448/000-030
1
DNV +
Protective coating
2787-2448/000-070
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x AC 200 ... 240 V
Input voltage range
1 x AC 180 ... 264 V
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 4.3 A (240 VAC; nominal load);
≤ 5.1 A (200 VAC; nominal load)
Inrush current
≤ 10 A (after 1 ms)
Power factor
≥ 0.98 (240 VAC)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 25 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
40 A (24 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 60 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
Communication interface, can be used with WAGO USB
Communication Cable (750-923) or IO-Link Communica
-
tion Module (2789-9080), Modbus RTU Communication
Module (2789-9015) or Modbus TCP Communication
Module (2789-9052)
Efficiency/power losses
Power loss P
l
≤ 1.5 W (standby); ≤ 2.4 W (no load);
≤ 40 W (230 VAC; nominal load)
Efficiency (typ.)
96 % (230 VAC; 40 A; 25 °C);
96.3 % (230 VAC; 30 A; 25 °C)
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 900,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> +55 °C)
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP® / Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data
Width x Height x Depth from upper-edge of DIN-rail
120 x 130 x 130 (mm) / 4.724 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 169 mm
Mounting type
DIN-35 rail
Weight
1900 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
17
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
2787 Series
Power supply; Pro 2; 1-phase; 48 VDC output voltage; 2.5 A output current;
TopBoost + PowerBoost; Communication capability
Power supply; Pro 2; 1-phase; 48 VDC output voltage;
2.5 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2154
1
Features
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 1.3 A (240 VAC; nominal load)
Inrush current
≤ 11 A (after 1 ms)
Power factor correction (PFC)
Active
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
48 ... 56 VDC (adjustable)
Nominal output current I
o nom
2.5 A (48 VDC)
Nominal output power
120 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 7.5 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
Communication interface, can be used with WAGO USB
Communication Cable (750-923) or IO-Link Communica
-
tion Module (2789-9080), Modbus RTU Communication
Module (2789-9015) or Modbus TCP Communication
Module (2789-9052)
Efficiency/power losses
Power loss Pl
≤ 0.8 W (standby); ≤ 1.7 W (no load);
≤ 9 W (230 VAC; nominal load)
Efficiency (typ.)
95.3 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 900,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
35 x 130 x 130 (mm) / 1.38 x 5.118 x 5.118 (inches)
Note (dimensions)
Height with connector: 166 mm
Mounting type
DIN-35 rail
Weight
650 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
18
1
www.wago.com
−
−
−
+
+
3
N
L
DI−
DI+
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
2787 Series
Power supply; Pro 2; 1-phase; 48 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; Communication capability
Power supply; Pro 2; 1-phase; 48 VDC output voltage;
10 A output current; TopBoost + PowerBoost; Commu
-
nication capability
Item No.
PU
2787-2157
1
Features:
•
Power supply with TopBoost, PowerBoost and configu
-
rable overload behavior
•
Configurable digital signal input and output, optical sta
-
tus indication, function keys
•
Communication interface for configuration and monito
-
ring
•
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Pluggable connection technology
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 130 ... 240 VDC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 5.9 A (240 VAC; nominal load)
Inrush current
≤ 12 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 24 ms (230 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
48 ... 56 VDC (adjustable)
Nominal output current I
o nom
10 A (48 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
DC 15 A (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
Communication interface, can be used with WAGO USB
Communication Cable (750-923) or IO-Link Communica
-
tion Module (2789-9080), Modbus RTU Communication
Module (2789-9015) or Modbus TCP Communication
Module (2789-9052)
Efficiency/power losses
Power loss Pl
≤ 1.3 W (standby); ≤ 2.6 W (no load);
≤ 24 W (230 VAC; nominal load)
Efficiency (typ.)
95.3 %
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
70 x 130 x130 (mm) / 2.756 x 5.118 x 5.118 (inches)
Note (dimensions)
Height without connector; Height with connector: 166
mm
Mounting type
DIN-35 rail
Weight
1450 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
19
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Communication module; Modbus TCP; Communication
capability
Item No.
PU
2789-9052
1
Features:
•
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
•
Modbus TCP/UDP
•
Suitable for monitoring the subordinate power supply
•
Function blocks for standard control systems available
upon request
•
Integrated ETHERNET switch for convenient wiring
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Communication module; Modbus TCP; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Nominal input current at U
N
210 mA (typ.)
Signaling and communication
Signaling
1 x ERR LED (red); 1 x COM OK LED (green);
1 x LED LNK/ACTx (green); 1 x LED SPEEDx (orange)
Communication
Modbus (TCP, UDP)
ETHERNET protocols
HTTP(S); BootP; DHCP; SNTP
Configuration options
Web-Based Management
Visualization
Web-Visu
Baud rate
100 MBd (ETHERNET: 10/100 Mbit/s)
Transmission medium (communication/fieldbus)
ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5
Safety and protection
Test voltage (fieldbus)
0.775 kVAC; 50 Hz; 1 min
Protection class/type
III / IP20; per EN 60529
Insulation type
Functional insulation
Overvoltage category
III
Pollution degree
2
Connection data
Connection type
Modbus TCP/UDP
Connector
2 x RJ-45
Cable length (max.)
100 m
Transmission medium
ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5
Physical data/Mechanical data/Material data
Width x Height x Depth
35 x 80 x 22 (mm) / 1.378 x 3.15 x 0.866 inches
Note (dimensions)
Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
45 g
Environmental requirements
Ambient temperature (operation at U
N
)
-40 ... +55 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
20
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Communication module; Modbus RTU; RJ45; Communi
-
cation capability
Item No.
PU
2789-9015
1
Features:
•
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
•
Modbus RTU (RS-485)
•
Suitable for monitoring the subordinate power supply
•
Function blocks for standard control systems available
upon request
•
Pluggable connection technology
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
•
Requires RJ-45 terminating resistor (120 Ω) for long
cables (2789-9915)
Communication module; Modbus RTU; RJ45; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Input voltage range
4.5 ... 5.5 VDC (SELV)
Input current I
i
≤ 0.04 A
Signaling and communication
Signaling
1 x LED PWR (green); 1 x LED RxD (yellow);
1 x LED TxD (yellow)
Communication
Modbus RTU via RS-485
Baud rate
4.8 ... 115.2 kBd
Number of devices (max.)
247
Transmission medium (communication/fieldbus)
Shielded copper cable
Safety and protection
Test voltage (input/output)
AC 2 kV; 50 Hz; 1 min
Test voltage (input/output/shield)
1 kVAC; 50 Hz; 1 min
Protection class/type
III / IP20; per EN 60529
Insulation type
Functional insulation
Pollution degree
2
Connection data
Connector
2 x RJ-45
Transmission medium
Shielded copper cable
Physical data/Mechanical data/Material data
Width x Height x Depth
35 x 80 x 22 (mm) / 1.378 x 3.15 x 0.866 inches
Note (dimensions)
Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
35 g
Environmental requirements
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201; UL HazLoc
21
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Communication module; IO-Link; Communication
capability
Item No.
PU
2789-9080
1
Features:
•
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
•
IO-Link device supports IO-Link specification 1.1
•
Suitable for configuring and monitoring the subordinate
power supply
•
Function blocks for standard control systems available
upon request
•
Pluggable connection technology
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Communication module; IO-Link; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
24 VDC (SELV; via IO-Link Master)
Input voltage range
18 ... 30 VDC (SELV; via IO-Link Master)
Input current I
i
≤ 0.015 A
Signaling and communication
Signaling
1 x COM OK LED (green); 1 x ERR LED (red)
Communication
IO-Link
IO-Link version
1.1
Baud rate
230.4 kBd (COM 3)
Data width
5 bytes
Data update rate
25 ms
Safety and protection
Isolation
0.63 kVDC
Protection class/type
III / IP20; per EN 60529
Pollution degree
2
Connection data
Connection technology
CAGE CLAMP®
Solid conductor
0.08 ... 2.5 mm² / 28 ... 12 AWG
Fine-stranded conductor
0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth
35 x 95 x 22 (mm) / 1.378 x 3.74 x 0.866 (inches)
Note (dimensions)
Height with connector; Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
35 g
Environmental requirements
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201; UL HazLoc
22
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Nominal input current at U
N
250 mA (max.)
Signaling and communication
Signaling
1 x ERR LED (red); 1 x COM OK LED (green);
1 x LED LNK/ACTx (green); 1 x LED SPEEDx (orange)
Communication
EtherNet/IPTM
ETHERNET protocols
HTTP(S); BootP; DHCP; SNTP; MQTT
Configuration options
Web-Based Management
Visualization
Web-Visu
Baud rate
100 MBd (ETHERNET: 10/100 Mbit/s)
Transmission medium (communication/fieldbus)
ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5
Safety and protection
Test voltage (fieldbus)
0.775 kVAC; 50 Hz; 1 min
Protection class/type
III / IP20; per EN 60529
Insulation type
Functional insulation
Overvoltage category
III
Pollution degree
2
Connection data
Connection type
EtherNet/IP
Connector
2 x RJ-45
Cable length (max.)
100 m
Transmission medium
ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5
Physical data/Mechanical data/Material data
Width x Height x Depth
35 x 80 x 22 (mm) / 1.378 x 3.15 x 0.866 (inches)
Note (dimensions)
Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
45 g
Environmental requirements
Ambient temperature (operation at U
N
)
-40 ... +55 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
Communication module; EtherNet/IP; Communication
capability
Item No.
PU
2789-9023
1
Features:
•
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
•
Ethernet/IP + MQTT
•
Suitable for monitoring the subordinate power supply
•
Function blocks for standard control systems available
upon request
•
Integrated ETHERNET switch for convenient wiring
•
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Communication module; EtherNet/IP; Communication capability
2789 Series
23
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 24 VDC output voltage; 3 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 24 VDC
output voltage; 3 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-818
1
Feaures
:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-5 %/V (< 95 VAC)
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 0.51 A (240 VAC; 3 ADC)
Inrush current
≤ 30 A (peak)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 70 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 29.5 VDC (adjustable)
Nominal output current I
o nom
3 A (24 VDC)
Nominal output power
72 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
6 ADC (4 s); 4.5 ADC (8 s)
TopBoost
14 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.5 W (standby); ≤ 3 W (no load); ≤ 8.8 W (nominal load)
Efficiency (typ.)
87.8 %
Circuit protection
Internal fuse
T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
40 x 163 x 163 (mm) / 1.575 x 6.417 x 6.417 (inches)
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
960 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
24
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 24 VDC output voltage; 5 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 24 VDC
output voltage; 5 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-822
1
Features:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 0.97 A (240 VAC; 5 ADC)
Inrush current
≤ 30 A (peak)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 35 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 29.5 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
10 ADC (4 s); 7.5 ADC (8 s)
TopBoost
21 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.5 W (standby); ≤ 5 W (no load);
≤ 14.6 W (nominal load)
Efficiency (typ.)
87.8 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data
Width
57 x 163 x 163 (mm) / 2.244 x 6.417 x 6.417 inches
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
1268 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
25
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 24 VDC
output voltage; 10 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-832
1
Features:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 1.2 A (240 VAC; 10 ADC)
Inrush current
≤ 8 A (active power factor correction (PFC))
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 24 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 29.5 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
20 ADC (4 s); 15 ADC (8 s)
TopBoost
60 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 3.8 W (no load);
≤ 24 W (nominal load)
Efficiency (typ.)
90 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
57 x 163 x 179 (mm) / 2.244 x 6.417 x 7.047 (inches)
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
1472.2 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
26
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 24 VDC
output voltage; 20 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-834
1
Features:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-1.5 %/V (< 110 VAC)
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 2.3 A (230 VAC; 20 ADC)
Inrush current
≤ 8 A (active power factor correction (PFC))
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 25 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 29.5 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
30 ADC (4 s); 25 ADC (8 s)
TopBoost
80 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 4.8 W (no load);
≤ 43.2 W (nominal load)
Efficiency (typ.)
91 %
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data
Width
97 x 171 x 187 (mm) / 3.819 x 6.732 x 7.362 (inches)
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
2300 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
27
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 48 VDC output voltage; 5 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 48 VDC
output voltage; 5 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-833
1
Features:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-1.5 %/V (< 110 VAC)
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 1.2 A (230 VAC; 5 ADC)
Inrush current
≤ 8 A (active power factor correction (PFC))
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
DC 33 ... 52 V (adjustable)
Nominal output current I
o nom
5 A (48 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
10 ADC (4 s); 7.5 ADC (8 s)
TopBoost
30 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 7.4 W (no load);
≤ 21.6 W (nominal load)
Efficiency (typ.)
91 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
57 x 163 x 179 (mm) / 2.244 x 6.417 x 7.047 (inches)
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
1475 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
28
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Pro; 1-phase; 48 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 1-phase; 48 VDC
output voltage; 10 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-835
1
Features:
•
Switched-mode power supply with PowerBoost and
TopBoost
•
Switch off the output and minimize power consumption
via stand-by input
•
Output monitoring via DC OK contact
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-1.5 %/V (< 110 VAC)
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 2.3 A (230 VAC; 10 ADC)
Inrush current
≤ 8 A (active power factor correction (PFC))
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
DC 33 ... 52 V (adjustable)
Nominal output current I
o nom
10 A (48 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
17.5 ADC (4 s); 15 ADC (8 s)
TopBoost
60 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 4.8 W (no load);
≤ 43.2 W (nominal load)
Efficiency (typ.)
91 %
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
Push-in CAGE CLAMP®; CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
97 x 171 x 187 (mm) / 3.819 x 6.732 x 7.362 (inches)
Note (dimensions)
Height with connector
Mounting type
DIN-35 rail
Weight
2460 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
29
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 12 VDC output voltage; 2 A output current;
NEC Class 2; DC OK signal
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Limited Power Source (LPS) per NEC Class 2
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Similar to pictured device
787 Series
Switched-mode power supply; Classic; 1-phase;
12 VDC output voltage; 2 A output current;
NEC Class 2; DC OK signal
Item No.
PU
787-1601
1
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.29 A (240 VAC); ≤ 0.5 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
11.5 ... 14.5 VDC (adjustable)
Nominal output current I
o nom
2 A (12 VDC); 2.1 A (< 40 °C)
Nominal output power
24 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 0.7 W; ≤ 5.3 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
5.7 W (100 VAC / 12 VDC; 2 A)
Efficiency (typ.)
82 %
Circuit protection
Internal fuse
T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
22.5 x 90 x 107.5 mm / 0.886 x 3.543 x 4.232 (inches)
Mounting type
DIN-35 rail
Weight
128 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
30
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 12 VDC output voltage; 4 A output current;
NEC Class 2; DC OK signal
787 Series
Switched-mode power supply; Classic; 1-phase;
12 VDC output voltage; 4 A output current;
NEC Class 2; DC OK signal
Item No.
PU
787-1611
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Limited Power Source (LPS) per NEC Class 2
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.46 A (240 VAC); ≤ 0.86 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
11.5 ... 14.5 VDC (adjustable)
Nominal output current I
o nom
4 A (12 VDC); 4.2 A (< 40 °C)
Nominal output power
48 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 8 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
9.1 W (100 VAC / 12 VDC; 4 A)
Efficiency (typ.)
86 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
45 x 90 x 107.5 (mm) / 1.772 x 3.543 x 4.232 (inches)
Mounting type
DIN-35 rail
Weight
257.6 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
31
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Similar to pictured device
Switched-mode power supply; Classic; 1-phase;
12 VDC output voltage; 7 A output current;
DC OK signal
Item No.
PU
787-1621
1
Switched-mode power supply; Classic; 1-phase; 12 VDC output voltage; 7 A output current;
DC OK signal
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.9 A (240 VAC); ≤ 1.66 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
11.5 ... 14.5 VDC (adjustable)
Nominal output current I
o nom
7 A (12 VDC); 7.5 A (< 40 °C)
Nominal output power
84 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 16.2 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
19.8 W (100 VAC / 12 VDC; 7 A)
Efficiency (typ.)
86 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 32 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
52 x 90 x 119 (mm) / 2.047 x 3.543 x 4.685 (inches)
Mounting type
DIN-35 rail
Weight
384 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
32
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 12 VDC output voltage; 15 A output current;
TopBoost; DC OK contact
787 Series
Similar to pictured device
Switched-mode power supply; Classic; 1-phase;
12 VDC output voltage; 15 A output current;
TopBoost; DC OK contact
Item No.
PU
787-1631
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 100 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.93 A (240 VAC); ≤ 2.05 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 28 ms (230 VAC); ≥ 28 ms (100 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
DC 11.5 ... 15 V (adjustable)
Nominal output current I
o nom
15 A (12 VDC)
Nominal output power
180 W
Residual ripple
≤ 35 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 4.4 W; ≤ 21.8 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
24.7 W (100 VAC / 12 VDC; 15 A)
Efficiency (typ.)
90 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 20 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 60 °C, 196... 264 VAC);
-2.5 %/K (> 50 °C, 85 ... 195 VAC)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
55 x 127 x 172 (mm) / 2.165 x 5 x 6.772 (inches)
Mounting type
DIN-35 rail
Weight
930 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
33
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Limited Power Source (LPS) per NEC Class 2
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 1 A output current;
NEC Class 2; DC OK signal
787 Series
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 1 A output current;
NEC Class 2; DC OK signal
Item No.
PU
787-1602
1
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.28 A (240 VAC); ≤ 0.49 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 20 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
1 A (24 VDC); 1.2 A (< 40 °C)
Nominal output power
24 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 4 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
5 W (100 VAC / 24 VDC; 1 A)
Efficiency (typ.)
86 %
Circuit protection
Internal fuse
T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 39 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
22.5 x 90 x 107.5 (mm) / 0.886 x 3.543 x 4.232 (inches)
Mounting type
DIN-35 rail
Weight
128 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
34
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Similar to pictured device
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 2 A output current;
NEC Class 2; DC OK signal
Item No.
PU
787-1606
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Limited Power Source (LPS) per NEC Class 2
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 2 A output current;
NEC Class 2; DC OK signal
787 Series
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.48 A (240 VAC); ≤ 0.82 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 20 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
2 A (24 VDC); 2.2 A (< 40 °C)
Nominal output power
48 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 6 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
7 W (100 VAC / 24 VDC; 2 A)
Efficiency (typ.)
89 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 37 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
45 x 90 x 107.5 (mm) / 1.772 x 3.543 x 4.232 (inches)
Mounting type
DIN-35 rail
Weight
210 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
35
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 3.8 A output current;
NEC Class 2; DC OK signal
787 Series
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 3.8 A output current;
NEC Class 2; DC OK signal
Item No.
PU
787-1616/000-1000
1
Similar to pictured device
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Limited Power Source (LPS) per NEC Class 2
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.95 A (240 VAC); ≤ 1.73 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
3.8 A (24 VDC)
Nominal output power
91.2 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
3.8 A (3.2 A at Uo > 25 VDC); LPS per NEC Class 2
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 2.8 W; ≤ 14 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
20 W (100 VAC / 91 W)
Efficiency (typ.)
87 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
52 x 90 x 119 (mm) / 2.047 x 3.543 x 4.685 (inches)
Mounting type
DIN-35 rail
Weight
384 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; UL 1310; DNV
36
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 4 A output current;
DC OK signal
787 Series
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 4 A output current;
DC OK signal
Item No.
PU
787-1616
1
With coated PCBs
787-1616/000-070
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.98 A (240 VAC); ≤ 1.82 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
4 A (24 VDC); 4.2 A (< 40 °C)
Nominal output power
96 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 12.4 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
15 W (100 VAC / 24 VDC; 4 A)
Efficiency (typ.)
89 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
52 x 90 x 119.5 (mm) / 2.047 x 3.543 x 4.705 (inches)
Mounting type
DIN-35 rail
Weight
384 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
37
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 5 A output current;
TopBoost; DC OK contact
787 Series
Similar to pictured device
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 5 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1622
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 97 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 1.24 A (230 VAC); ≤ 2.3 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 10 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 30 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1.2 W; ≤ 14.6 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
19.4 W (100 VAC / 24 VDC; 5 A)
Efficiency (typ.)
89 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 41 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 60 °C, AC 196... 264 V); -2,5 %/K (> 50 °C, AC
85 ... 195 V)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
42 x 127 x 137.5 (mm) / 1.654 x 5 x 5.394 (inches)
Mounting type
DIN-35 rail
Weight
477.6 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
38
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 10 A output current;
TopBoost; DC OK contact
787 Series
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 10 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1632
1
With coated PCBs
787-1632/000-070
1
Similar to pictured device
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 100 ... 300 VDC
Input voltage derating
-2.5 %/V (< 100 VAC); -1 %/V (< 130 VDC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 1.25 A (230 VAC); ≤ 2.74 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 17 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 50 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 6.6 W; ≤ 24.4 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
31.3 W (100 VAC / 24 VDC; 10 A)
Efficiency (typ.)
91 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 60 °C, 196... 264 VAC);
-2.5 %/K (> 50 °C, 85 ... 195 VAC)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
55 x 127 x 172 (mm) / 2.165 x 5 x 6.772 (inches)
Mounting type
DIN-35 rail
Weight
1140 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
39
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 24 VDC output voltage; 20 A output current;
TopBoost; DC OK contact
787 Series
Switched-mode power supply; Classic; 1-phase;
24 VDC output voltage; 20 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1634
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-1.8 %/V (< 105 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 2.23 A (230 VAC); ≤ 5.56 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC); ≥ 8 ms (100 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 7.2 W; ≤ 42.4 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
68.3 W (100 VAC / 24 VDC; 20 A)
Efficiency (typ.)
92 %
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
−5 %/K (> 60 °C, 196... 264 VAC);
−2.5 %/K (> 50 °C, 85 ... 195 VAC)
Connection data
Connection technology
Push-in CAGE CLAMP®; CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
95 x 127 x 170 (mm) / 3.74 x 5 x 6.693 (inches)
Mounting type
DIN-35 rail
Weight
1600 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
40
1
www.wago.com
L
DC+
DC+
DC -
DC -
DC O.K.
N
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Bounce-free switching signal (DC OK)
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 48 VDC output voltage; 2 A output current;
DC OK signal
787 Series
Switched-mode power supply; Classic; 1-phase;
48 VDC output voltage; 2 A output current;
DC OK signal
Item No.
PU
787-1623
1
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 0.97 A (240 VAC); ≤ 1.84 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 80 ms (230 VAC); ≥ 15 ms (100 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
40 ... 53 VDC (adjustable)
Nominal output current I
o nom
2 A (48 VDC); 2.1 A (< 40 °C)
Nominal output power
96 W
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1 W; ≤ 16.2 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
19.8 W (100 VAC / 48 VDC; 2 A)
Efficiency (typ.)
86 %
Circuit protection
Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Protection class/type
II / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 60 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
52 x 90 x 119 (mm) / 2.047 x 3.543 x 4.685 (inches)
Mounting type
DIN-35 rail
Weight
590 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; EN 60335-1;
UL 60950-1; UL 508; DNV
41
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 1-phase;
48 VDC output voltage; 5 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1633
1
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 48 VDC output voltage; 5 A output current;
TopBoost; DC OK contact
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval, also suitable for EMC 1 in conjunction
with 787-980 Filter Module
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 100 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 1.25 A (230 VAC); ≤ 2.74 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 21 ms (230 VAC); ≥ 21 ms (100 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
40 ... 56 VDC (adjustable)
Nominal output current I
o nom
5 A (48 VDC)
Nominal output power
240 W
Residual ripple
≤ 30 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 7 W; ≤ 40.8 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
26.5 W (100 VAC / 48 VDC; 5 A)
Efficiency (typ.)
92 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 60 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 60 °C, 196... 264 VAC);
-2.5 %/K (> 50 °C, 85 ... 195 VAC)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
55 x 127 x 172 (mm) / 2.165 x 5 x 6.772 (inches)
Mounting type
DIN-35 rail
Weight
930 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
42
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Similar to pictured device
Switched-mode power supply; Classic; 1-phase; 48 VDC output voltage; 10 A output current;
TopBoost; DC OK contact
787 Series
Switched-mode power supply; Classic; 1-phase;
48 VDC output voltage; 10 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1635
1
With coated PCBs
787-1635/000-070
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
•
DNV approval
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 85 ... 264 VAC; 120 ... 300 VDC
Input voltage derating
-2.5 %/V (< 100 VAC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 2.23 A (230 VAC); ≤ 5.56 A (100 VAC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC); ≥ 20 ms (100 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
40 ... 56 VDC (adjustable)
Nominal output current I
o nom
10 A (48 VDC)
Nominal output power
480 W
Residual ripple
≤ 80 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 11.7 W; ≤ 36.3 W (230 VAC; nominal load)
Power loss (max.) P
l (max.)
64.9 W (100 VAC / 48 VDC; 10 A)
Efficiency (typ.)
93 %
Circuit protection
Internal fuse
T 10 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 60 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 60 °C, 196... 264 VAC);
-2.5 %/K (> 50 °C, 85 ... 195 VAC)
Connection data
Connection technology
Push-in CAGE CLAMP®; CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
95 x 127 x 170 (mm) / 3.74 x 5 x 6.693 (inches)
Mounting type
DIN-35 rail
Weight
1600 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
43
1
www.wago.com
L1 (L)
L2 (N)
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Features:
•
Switched-mode power supply with TopBoost, enabling
secondary-side protection via circuit breakers
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60950-1/UL 60950-1; PELV per EN 60204
Switched-mode power supply; Classic; 2-phase; 24 VDC output voltage; 5 A output current;
TopBoost; DC OK contact
787 Series
Switched-mode power supply; Classic; 2-phase;
24 VDC output voltage; 5 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1628
1
Input
Phases
1 / 2
Nominal input voltage U
i nom
(1 / 2) x 200 ... 500 VAC
Input voltage range
(1 / 2) x 180 ... 550 VAC; 254 ... 780 VDC
Input voltage derating
-0.5 %/V (< 200 VAC); -0.4 %/V (< 280 VDC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 1.25 A (200 VAC); ≤ 0.67 A (500 VAC)
Inrush current
≤ 30 A (NTC)
Power factor
≥ 0.52
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 126 ms (500 VAC); ≥ 15 ms (200 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 30 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 0.94 W; ≤ 16.36 W (230 VAC; nominal load);
≤ 14.55 W (400 VAC; nominal load)
Power loss (max.) P
l (max.)
18.2 W (200 VAC / 24 VDC; 5 A)
Efficiency (typ.)
89 %
Circuit protection
Internal fuse
T 3.15 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-2.5 %/K (> 55 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
42 x 127 x 143.5 (mm) / 1.654 x 5 x 5.65 (inches)
Mounting type
DIN-35 rail
Weight
600 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
44
1
www.wago.com
L1 (L)
L2 (N)
DC+
DC+
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Classic; 2-phase;
24 VDC output voltage; 10 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1638
1
Features:
•
Switched-mode power supply with TopBoost, enabling
secondary-side protection via circuit breakers
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
DC OK contact
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60950-1/UL 60950-1; PELV per EN 60204
Switched-mode power supply; Classic; 2-phase; 24 VDC output voltage; 10 A output current;
TopBoost; DC OK contact
787 Series
Input
Phases
1 / 2
Nominal input voltage U
i nom
(1 / 2) x 200 ... 500 VAC
Input voltage range
(1 / 2) x 180 ... 550 VAC; 254 ... 780 VDC
Input voltage derating
-0.5 %/V (< 200 VAC); -0.4 %/V (< 280 VDC)
Nominal mains frequency range
44 ... 66 Hz; 0 Hz
Input current I
i
≤ 1.975 A (230 VAC); ≤ 1.36 A (230 VAC)
Inrush current
≤ 30 A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 78 ms (400 VAC); ≥ 20 ms (200 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 30 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 1.3 W; ≤ 27.8 W (230 VAC; nominal load);
≤ 20.3 W (400 VAC; nominal load)
Power loss (max.) P
l (max.)
27.8 W (230 VAC / 24 VDC; 10 A)
Efficiency (typ.)
89 % (230 VAC); 92.5 % (400 VAC)
Circuit protection
Internal fuse
T 6.3 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit; ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-2.5 %/K (> 55 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
55 x 127 x 146.5 (mm) / 2.165 x 5 x 5.768 (inches)
Mounting type
DIN-35 rail
Weight
830 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
45
1
www.wago.com
−
−
+
N
L
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Eco 2; 1-phase; 24 VDC output voltage;
1.25 A output current; DC OK LED
Item No.
PU
2687-2142
1
Features:
•
Optical status indication
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Connection technology with push-in termination and
tool-free lever operation
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010/UL 61010
•
Marker slot (2789-1223, not included) for WAGO mar
-
king cards (WMB) and WAGO marking strips
Power supply; Eco 2; 1-phase; 24 VDC output voltage; 1.25 A output current; DC OK LED
2687 Series
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 0.3 A (230 VAC; nominal load);
≤ 0.6 A (100 VAC; nominal load)
Inrush current
≤ 10 A (after 1 ms)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 15 ms (110 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 29 VDC (adjustable)
Nominal output current I
o nom
1.25 A (24 VDC)
Nominal output power
30 W
Residual ripple
≤ 30 mV (peak-to-peak, at 230 VAC)
Overload behavior
Constant power up to 125 %; Shutdown and automatic
restart in the event of a short circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Efficiency/power losses
Power loss P
l
≤ 0.2 W (no load); ≤ 4.3 W (nominal load)
Efficiency (typ.)
88 %
Circuit protection
Internal fuse
T 1 A / 250 VAC
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC)
3,510 V
Protection class/type
II / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,000,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See type label/manual
Operating altitude (max.)
5000 m
Connection data
Connection technology
Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.2 ... 4 mm² / 0.2 ... 4 mm² / 24 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
25 x 100 x 100 (mm) / 0.984 x 3.937 x 3.937 (inches)
Mounting type
DIN-35 rail
Weight
160 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
46
1
www.wago.com
3
−
−
−
+
+
N
L
DO−
DO+
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Power supply; Eco 2; 1-phase; 24 VDC output voltage; 5 A output current; DC OK contact
Power supply; Eco 2; 1-phase; 24 VDC output voltage;
5 A output current; DC OK contact
Item No.
PU
2687-2144
1
Features:
•
Signal output, optical status indication
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Connection technology with push-in termination and
tool-free lever operation
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010/UL 61010
•
Marker slot (2789-1233, not included) for WAGO mar
-
king cards (WMB) and WAGO marking strips
2687 Series
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 0.8 A (230 VAC; nominal load);
≤ 1.5 A (100 VAC; nominal load)
Inrush current
≤ 20 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 75 mV (peak-to-peak)
Overload behavior
Constant current up to 125 %; Shutdown and automatic
restart in the event of a short circuit
Signaling and communication
Signaling
Optical status indication (overload); Optical status indica
-
tion (DC OK); Digital signal output (DO)
Efficiency/power losses
Power loss P
l
≤ 3 W; ≤ 12 W (nominal load)
Efficiency (typ.)
90 %
Circuit protection
Internal fuse
T 3.15 A / 250 VAC
Backup fusing (recommended)
16 A (for USA/Canada: 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC)
3,510 V
Isolation voltage (pri.-PE, AC)
2,200 V
Isolation voltage (sec.-PE)
0.5 kVDC
Protection class / Protection type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/No
MTBF
> 1,000,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See type label
Operating altitude (max.)
5000 m
Connection data
Connection technology
Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.2 ... 4 mm² / 0.2 ... 4 mm² / 24 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
38 x 130 x 130 (mm) / 1.496 x 5.118 x 5.118 (inches)
Mounting type
DIN-35 rail
Weight
620 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
47
1
www.wago.com
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
−
−
+
N
L
Power supply; Eco 2; 1-phase; 24 VDC output voltage;
10 A output current; DC OK contact
Item No.
PU
2687-2146
1
Features:
•
Signal output, optical status indication
•
Suitable for both parallel and series operation
•
Natural convection cooling when horizontally mounted
•
Connection technology with push-in termination and
tool-free lever operation
•
Electrically isolated output voltage (SELV/PELV) per
EN 61010/UL 61010
•
Marker slot (2789-1233, not included) for WAGO mar
-
king cards (WMB) and WAGO marking strips
Power supply; Eco 2; 1-phase; 24 VDC output voltage; 10 A output current; DC OK contact
2687 Series
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 1.1 A (230 VAC; nominal load);
≤ 2.7 A (100 VAC; nominal load)
Inrush current
≤ 25 A (after 1 ms)
Power factor correction (PFC)
active
Mains failure hold-up time
≥ 25 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 75 mV (peak-to-peak)
Overload behavior
Constant current up to 105 ... 110 %; Shutdown and
automatic restart in the event of a short circuit
Signaling and communication
Signaling
Optical status indication (overload); Optical status indica
-
tion (DC OK); Digital signal output (DO)
Efficiency/power losses
Power loss P
l
≤ 3 W (230 VAC; no load); ≤ 13 W (230 VAC; nominal load)
Efficiency (typ.)
93 %
Circuit protection
Internal fuse
T 6.3 A / 250 VAC
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC)
3,510 V
Isolation voltage (pri.-PE, AC)
2,200 V
Isolation voltage (sec.-PE)
0.5 kVDC
Isolation voltage (sec.-signal)
0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K; > 45 °C
Operating altitude (max.)
5000 m
Connection data
Connection technology
Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.2 ... 4 mm² / 0.2 ... 4 mm² / 24 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
50 x 130 x 130 (mm) / 1.97 x 5.118 x 5.118 (inches)
Mounting type
DIN-35 rail
Weight
800 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
48
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Eco; 1-phase; 12 VDC output voltage; 2 A output current; DC OK
LED
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60335-1; PELV per EN 60204
•
DIN-35 rail mountable in different positions
•
Direct installation on mounting plate via cable grip
Switched-mode power supply; Eco; 1-phase; 12 VDC
output voltage; 2 A output current; DC OK LED
Item No.
PU
787-1701
1
Similar to pictured device
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 125 ... 375 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 0.7 A (100 VAC)
Inrush current
≤ 18 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (230 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
10 ... 14 VDC (adjustable)
Nominal output current I
o nom
2 A (12 VDC; 110 ... 240 VAC);
1.6 A (12 VDC; 100 ... 240 VAC)
Nominal output power
24 W
Residual ripple
≤ 150 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 6 W (230 VAC; 12 VDC; 2 A)
Efficiency (typ.)
80 % (230 VAC; 2 ADC)
Circuit protection
Internal fuse
F 1 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: B6, B10
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes, for 2 devices of the same type
MTBF
> 300,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +60 °C
Ambient temperature (storage)
-25 ... +75 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-4 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
30 x 90 x 99
Mounting type
DIN-35 rail; Screw mount
Weight
250 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61204-3; EN 60335-1; EN 61558-2-6; EN 62368-1
49
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Eco; 1-phase; 12 VDC output voltage; 4 A output current;
DC OK LED
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60335-1; PELV per EN 60204
•
DIN-35 rail mountable in different positions
•
Direct installation on mounting plate via cable grip
Switched-mode power supply; Eco; 1-phase; 12 VDC
output voltage; 4 A output current; DC OK LED
Item No.
PU
787-1711
1
Similar to pictured device
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 125 ... 375 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 1.8 A (100 VAC)
Inrush current
≤ 18 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (230 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
10 ... 14 VDC (adjustable)
Nominal output current I
o nom
4 A (12 VDC; 110 ... 240 VAC);
3.2 A (12 VDC; 100 ... 240 VAC)
Nominal output power
48 W
Residual ripple
≤ 150 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 9.6 W (230 VAC; 12 VDC; 4 A)
Efficiency (typ.)
80 % (230 VAC; 4 ADC)
Circuit protection
Internal fuse
F 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: B6, B10
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes, for 2 devices of the same type
MTBF
> 300,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +60 °C
Ambient temperature (storage)
-25 ... +75 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-4 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
40 x 90 x 99
Mounting type
DIN-35 rail; Screw mount
Weight
250 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61204-3; EN 60335-1; EN 61558-2-6; EN 62368-1
50
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Eco; 1-phase; 12 VDC output voltage; 8 A output current;
DC OK LED
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60335-1; PELV per EN 60204
•
DIN-35 rail mountable in different positions
•
Direct installation on mounting plate via cable grip
Switched-mode power supply; Eco; 1-phase;
12 VDC output voltage; 8 A output current; DC OK LED
Item No.
PU
787-1721
1
Similar to pictured device
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 125 ... 375 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 A (100 VAC)
Inrush current
≤ 18 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (230 VAC)
Output
Nominal output voltage U
o nom
12 VDC (SELV)
Output voltage range
10 ... 14 VDC (adjustable)
Nominal output current I
o nom
8 A (12 VDC; 110 ... 240 VAC);
6.4 A (12 VDC; 100 ... 240 VAC)
Nominal output power
96 W
Residual ripple
≤ 150 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 20 W (230 VAC; 12 VDC; 8 A)
Efficiency (typ.)
80 % (230 VAC; 8 ADC)
Circuit protection
Internal fuse
F 3.15 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: B6, B10
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes, for 2 devices of the same type
MTBF
> 300,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +60 °C
Ambient temperature (storage)
-25 ... +75 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-3 %/K (> 40 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
60 x 130 x 99
Mounting type
DIN-35 rail; Screw mount
Weight
520 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61204-3; EN 60335-1; EN 61558-2-6; EN 62368-1
51
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Eco; 1-phase;
24 VDC output voltage; 1.25 A output current;
DC OK LED
Item No.
PU
787-1702
1
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60335-1 and UL 60950-1; PELV per EN 60204
•
DIN-35 rail mountable in different positions
•
Direct installation on mounting plate via cable grip
Switched-mode power supply; Eco; 1-phase; 24 VDC output voltage; 1.25 A output current;
DC OK LED
787 Series
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 125 ... 375 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 0.3 A (230 VAC); ≤ 0.6 A (115 VAC)
Inrush current
≤ 18 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 26 VDC (adjustable)
Nominal output current I
o nom
1.25 A (24 VDC; 110 ... 240 VAC);
1 A (24 VDC; 100 ... 240 VAC)
Nominal output power
30 W
Residual ripple
≤ 200 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 6 W (230 VAC; 24 VDC; 1.25 A)
Efficiency (typ.)
87 % (230 VAC; 1.25 ADC)
Circuit protection
Internal fuse
F 1 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: B6, B10
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes, for 2 devices of the same type
MTBF
> 300,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +60 °C
Ambient temperature (storage)
-25 ... +75 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-4 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
30 x 90 x 99
Mounting type
DIN-35 rail; Screw mount
Weight
257 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61204-3; EN 60335-1; EN 62368-1; UL 60950-1;
UL 508
52
1
www.wago.com
L
N
DC+
DC+
DC -
DC -
WAGO Power Supplies
Section 1 | WAGO Power Supplies; 1-Phase
Switched-mode power supply; Eco; 1-phase;
24 VDC output voltage; 2.5 A output current;
DC OK LED
Item No.
PU
787-1712
1
Switched-mode power supply; Eco; 1-phase; 24 VDC output voltage; 2.5 A output current;
DC OK LED
787 Series
Features:
•
Switched-mode power supply
•
Natural convection cooling when horizontally mounted
•
Encapsulated for use in control cabinets
•
Suitable for both parallel and series operation
•
Electrically isolated output voltage (SELV) per
EN 60335-1 and UL 60950-1; PELV per EN 60204
•
DIN-35 rail mountable in different positions
•
Direct installation on mounting plate via cable grip
Input
Phases
1
Nominal input voltage U
i nom
1 x 100 ... 240 VAC
Input voltage range
1 x 90 ... 264 VAC; 125 ... 375 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 0.6 A (230 VAC); ≤ 1.2 A (115 VAC)
Inrush current
≤ 18 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (230 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 26 VDC (adjustable)
Nominal output current I
o nom
2.5 A (24 VDC; 110 ... 240 VAC);
2 A (24 VDC; 100 ... 240 VAC)
Nominal output power
60 W
Residual ripple
≤ 200 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 12 W (230 VAC; 24 VDC; 2.5 A)
Efficiency (typ.)
88 % (230 VAC; 2.5 ADC)
Circuit protection
Internal fuse
F 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: B6, B10
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes, for 2 devices of the same type
MTBF
> 300,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +60 °C
Ambient temperature (storage)
-25 ... +75 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-4 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail
40 x 90 x 99
Mounting type
DIN-35 rail; Screw mount
Weight
300 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61204-3; EN 60335-1; EN 62368-1; UL 60950-1;
UL 508
53
1
您正在使用的浏览器版本过低,将不能正常浏览产品选型内容。
- 收藏