Section 2 | WAGO Power Supplies; 3-Phase
Nominal voltage (output)
Nominal current (output)
[ADC]
Approvals
DC OK signal/
contact
RS-232 interface
TopBoost
1)
PowerBoost
Efficiency
typ. [%]
Ambient
temperature [°C]
4)
Item Number
Page
EN 60335
cURus 60950
cULus 508
cULus 61010
DNV
ANSI/ISA 12.12.1
ATEX/IEC Ex
24 VDC
5,00
92,5
−25 ... +70
2787-2344
84
6,25
87,0
−25 ... +70
787-738
105
10,0
93,0
−25 ... +70
2787-2346
85
10,0
95,0
−25 ... +70
2787-2357
88
10,0
91,7
−25 ... +70
787-840
94
10,0
91,7
−25 ... +70
787-850
97
10,0
90,0
−25 ... +70
787-1640
102
10,0
89,0
−25 ... +70
787-740
106
20,0
94,8
−25 ... +70
2787-2347
86
20,0
96.0
−25 ... +70
2787-2358
89
20,0
92,9
−25 ... +70
787-842
95
20,0
92,9
−25 ... +70
787-852
98
20,0
92,0
−25 ... +70
787-1642
103
20,0
90,0
−25 ... +70
787-742
107
20,0
90,5
−20 ... +70
787-2742
108
40,0
95,0
−20 ... +70
2787-2348
87
40,0
93,6
−25 ... +55
787-844
96
40,0
93,6
−25 ... +55
787-854
99
40,0
92,0
−25 ... +70
787-1644
104
40,0
91,5
−20 ... +70
787-2744
109
48 VDC
10,0
93,0
−25 ... +70
787-845
100
20,0
94,4
−25 ... +70
787-847
101
■ yes
WAGO Power Supplies; 3-Phase
Selection Guide
82
2
www.wago.com
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
83
2
www.wago.com
L
N
DC+
DC–
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Power supply; Pro 2; 3-phase; 24 VDC output voltage; 5 A output current;
TopBoost + PowerBoost; Communication capability
Power supply; Pro 2; 3-phase; 24 VDC output voltage;
5 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2344
1
DNV
2787-2344/000-030
1
DNV +
Protective coating
2787-2344/000-070
1
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 0.4 A (400 VAC; 24 VDC / 5 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
5 A (24 VDC)
Nominal output power
120 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Efficiency (typ.)
92.5 % (230 VAC; 5 A; 25 °C)
Circuit protection
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,400,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
40 x 130 x 130; Height with connector: 166
Mounting type
DIN-35 rail
Weight
650 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
2787 Series
84
2
www.wago.com
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Power supply; Pro 2; 3-phase; 24 VDC output voltage;
10 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2346
1
DNV
2787-2346/000-030
1
DNV +
Protective coating
2787-2346/000-070
1
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Power supply; Pro 2; 3-phase; 24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; Communication capability
Serie 2787
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 0.6 A (400 VAC; 24 VDC / 10 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
15 ADC (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Power loss P
l
≤ 3 W (standby); ≤ 3 W (no load); ≤ 18 W (400 VAC;
nominal load)
Efficiency (typ.)
93 % (400 VAC; 10 A; 25 °C)
Circuit protection
Internal fuse
3 x T 2.5 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 1,000,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
50 x 130 x 130; Height with connector: 166
Mounting type
DIN-35 rail
Weight
1000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
85
2
www.wago.com
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Power supply; Pro 2; 3-phase; 24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Input voltage derating
See instruction leaflet
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 0.8 A (400 VAC; 24 VDC / 20 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
30 ADC (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Power loss P
l
≤ 3.6 W (standby); ≤ 4.4 W (no load); ≤ 21 W (400 VAC;
nominal load)
Efficiency (typ.)
95.9 % (400 VAC; 20 A; 25 °C)
Circuit protection
Internal fuse
3 x T 2.5 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
70 x 130 x 130; Height with connector: 169
Mounting type
DIN-35 rail
Weight
1400 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
Power supply; Pro 2; 3-phase; 24 VDC output voltage;
20 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2347
1
DNV
DNV
2787-2347/000-030
1
DNV +
Protective coating
2787-2347/000-070
1
86
2
www.wago.com
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Power supply; Pro 2; 3-phase; 24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; Communication capability
2787 Series
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
+ 2787-2348/000-030
+ 2787-2348/000-070
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Input voltage derating
See instruction leaflet
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 1.5 A (400 VAC; 24 VDC / 40 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
24 ... 28 VDC (adjustable)
Nominal output current I
o nom
40 A (24 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
60 ADC (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Efficiency (typ.)
96.1 % (400 VAC; 40 A; 25 °C)
Circuit protection
Internal fuse
3 x T 2.5 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Overvoltage protection; secondary
Internal protective circuit ≤ 35 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
120 x 130 x 130; Height with connector: 169
Mounting type
DIN-35 rail
Weight
2000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
Power supply; Pro 2; 3-phase; 24 VDC output voltage;
40 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2348
1
DNV
DNV
2787-2348/000-030
1
DNV +
Protective coating
2787-2348/000-070
1
87
2
www.wago.com
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Power supply; Pro 2; 3-phase; 48 VDC output voltage;
10 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2357
1
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Power supply; Pro 2; 3-phase; 48 VDC output voltage; 10 A output current; TopBoost + Power
-
Boost; Communication capability
2787 Series
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 0.8 A (400 VAC; 48 VDC / 10 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Nominal output current I
o nom
10 A (48 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
15 ADC (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Power loss P
l
≤ 3.6 W (standby); ≤ 4.4 W (no load); ≤ 21 W (nominal load)
Efficiency (typ.)
95 %
Circuit protection
Internal fuse
3 x T 3.15 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510 V / 2,200 V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 900,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
70 x 130 x 130; Height with connector: 169
Mounting type
DIN-35 rail
Weight
1400 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
88
2
www.wago.com
+
+
3
L3
L2
DI− DI+
DO− DO+
L1
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
2787 Series
Power supply; Pro 2; 3-phase; 48 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; Communication capability
Power supply; Pro 2; 3-phase; 48 VDC output voltage;
20 A output current; TopBoost + PowerBoost;
Communication capability
Item No.
PU
2787-2358
1
Features:
Power supply with TopBoost, PowerBoost and
configurable overload behavior
Configurable digital signal input and output, optical
status indication, function keys
Communication interface for configuration and
monitoring
Optional connection to IO-Link, EtherNet/IP, Modbus
TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per
EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Phases
3
Nominal input voltage U
i nom
3 x 400 ... 500 VAC (connection without neutral conduc
-
tor)
Input voltage range
3 x 340 ... 550 VAC
Nominal mains frequency range
50 ... 60 Hz
Input current I
i
≤ 3 x 1.6 A (400 VAC; 48 VDC / 20 A)
Inrush current
≤ 15 A (after 1 ms)
Power factor correction (PFC)
Active
Mains failure hold-up time
≥ 20 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
DC 48 ... 56 V (adjustable)
Nominal output current I
o nom
20 A (48 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Time-limited constant current
mode (other overload behaviors can be set)
PowerBoost
30 ADC (5 s)
TopBoost
Up to 600 %
Signaling and communication
Signaling
Digital signal input and output (DI/DO)
Communication
USB (Communication Cable 750-923);
Ethernet/IP (Communication Module 2789-9023);
IO-Link (Communication Module 2789-9080);
Modbus RTU (Communication Module 2789-9015);
Modbus TCP (Communication Module 2789-9052)
Efficiency/power losses
Efficiency (typ.)
96 %
Circuit protection
Internal fuse
2 x T 5 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x 16 A (for USA/Canada: 3 x 15 A)
Safety and protection/Environmental requirements
Isolation voltage (pri.-sec., AC/pri.-PE, AC/sec.-PE)
3,510V / 2,200V / 0.5 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
III (≤ 2000 m a.s.l.); II (> 2000 m a.s.l.)
Pollution degree
2
Transient suppression (primary)
Yes
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
See instruction leaflet
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®/Push-in CAGE CLAMP®
Input/Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
120 x 130 x 130; Height with connector: 169
Mounting type
DIN-35 rail
Weight
2000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
89
2
www.wago.com
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Communication module; Modbus TCP;
Communication capability
Item No.
PU
2789-9052
1
Features:
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
Modbus TCP/UDP
Suitable for monitoring the subordinate power supply
Function blocks for standard control systems available
upon request
Integrated ETHERNET switch for convenient wiring
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Communication module; Modbus TCP; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Nominal input current at U
N
210 mA (typ.)
Signaling and communication
Signaling
1 x ERR LED (red); 1 x COM OK LED (green);
1 x LED LNK/ACTx (green); 1 x LED SPEEDx (orange)
Communication
Modbus (TCP, UDP)
ETHERNET protocols
HTTP(S); BootP; DHCP; SNTP
Configuration options
Web-Based Management
Visualization
Web-Visu
Baud rate
100 MBd (ETHERNET: 10/100 Mbit/s)
Safety and protection/Environmental requirements
Test voltage (fieldbus)
0.775 kVAC; 50 Hz; 1 min
Protection class/type
III / IP20; per EN 60529
Insulation type
Functional insulation
Overvoltage category
III
Pollution degree
2
Ambient temperature (operation at U
N
)
-40 ... +55 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Connection data
Connection Technology
Modbus TCP/UDP; 2 x RJ-45
Cable length (max.)
100 m
Transmission medium
ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5
Physical data/Mechanical data/Material data
Width x Height x Depth (mm)
35 x 80 x 22; Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
45 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
90
2
www.wago.com
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Communication module; Modbus RTU; RJ45;
Communication capability
Item No.
PU
2789-9015
1
Features:
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
Modbus RTU (RS-485)
Suitable for monitoring the subordinate power supply
Function blocks for standard control systems available
upon request
Pluggable connection technology
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Requires RJ-45 terminating resistor (120 Ω) for long
cables (2789-9915)
Communication module; Modbus RTU; RJ45; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Input voltage range
DC 4.5 ... 5.5 V(SELV)
Input current I
i
≤ 0.04 A
Signaling and communication
Signaling
1 x LED PWR (green); 1 x LED RxD (yellow);
1 x LED TxD (yellow)
Communication
Modbus RTU via RS-485
Baud rate
4.8 ... 115.2 kBd
Number of devices (max.)
247
Safety and protection/Environmental requirements
Test voltage (input/output)
AC 2 kV; 50 Hz; 1 min
Test voltage (input/output/shield)
1 kVAC; 50 Hz; 1 min
Protection class
III
Insulation type
Functional insulation
Protection type
IP20; per EN 60529
Pollution degree
2
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Connection data
Connector
2 x RJ-45
Transmission medium
Shielded copper cable
Physical data/Mechanical data/Material data
Width x Height x Depth (mm)
35 x 80 x 22; Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
35 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201; UL HazLoc
91
2
www.wago.com
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Communication module; IO-Link; Communication
capability
Item No.
PU
2789-9080
1
Features:
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
IO-Link device supports IO-Link specification 1.1
Suitable for configuring and monitoring the subordinate
power supply
Function blocks for standard control systems available
upon request
Pluggable connection technology
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Communication module; IO-Link; Communication capability
2789 Series
Input
Nominal input voltage U
i nom
24 VDC (SELV; via IO-Link Master)
Input voltage range
18 ... 30 VDC (SELV; via IO-Link Master)
Input current I
i
≤ 0.015 A
Signaling and communication
Signaling
1 x COM OK LED (green); 1 x ERR LED (red)
Communication
IO-Link
IO-Link version
1.1
Baud rate
230.4 kBd (COM 3)
Data width
5 bytes
Data update rate
25ms
Safety and protection/Environmental requirements
Isolation
0.63 kVDC
Protection class/type
III / IP20; per EN 60529
Pollution degree
2
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Operating altitude (max.)
5000 m
Connection data
Connection technology
CAGE CLAMP®
Solid/Fine-stranded/AWG
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Cable length (max.)
20 m (IO-Link)
Physical data/Mechanical data/Material data
Width x Height x Depth (mm)
35 x 95 x 22; Height with connector; Depth in mounted
state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
35 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201; UL HazLoc
92
2
www.wago.com
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Communication module; EtherNet/IP; Communication capability
Communication module; EtherNet/IP;
Communication capability
Item No.
PU
2789-9023
1
Features:
WAGO‘s communication module snaps onto a Pro 2
Power Supply‘s communication interface.
Ethernet/IP + MQTT
Suitable for monitoring the subordinate power supply
Function blocks for standard control systems available
upon request
Integrated ETHERNET switch for convenient wiring
Marker slot for WAGO marking cards (WMB) and WAGO
marking strips
Input
Nominal input voltage U
i nom
5 VDC (SELV)
Nominal input current at U
N
250 mA (max.)
Signaling and communication
Signaling
1 x ERR LED (red); 1 x COM OK LED (green);
1 x LED LNK/ACTx (green); 1 x LED SPEEDx (orange)
Communication
ETHERNET protocols
EtherNet/IPTM; HTTP(S); BootP; DHCP; SNTP; MQTT
Configuration options
Web-Based Management
Visualization
Web-Visu
Baud rate
100 MBd (ETHERNET: 10/100 Mbit/s)
Safety and protection/Environmental requirements
Test voltage (fieldbus)
0.775 kVAC; 50 Hz; 1 min
Protection class/type
III / IP20; per EN 60529
Insulation type
Functional insulation
Overvoltage category
III
Pollution degree
2
Ambient temperature (operation at U
N
)
-40 ... +55 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
5 ... 95 % (no condensation permissible)
Operating altitude (max.)
5000 m
Connection data
Connection Technology
EtherNet/IP; 2 x RJ-45
Cable length (max.)
100 m
Transmission medium
ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5
Physical data/Mechanical data/Material data
Width x Height x Depth (mm)
35 x 80 x 22; Depth in mounted state
Mounting type
Snaps onto a Pro 2 Power Supply's communication
interface (X4)
Weight
45 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 61010-1;
UL 61010-2-201
2789 Series
93
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Switch off the output and minimize power consumption
via stand-by input
Output monitoring via DC OK contact
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
Item No.
PU
787-840
1
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 0.6 A (340 VAC; 10 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 22 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
20 ADC (4 s); 15 ADC (16 s)
TopBoost
70 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 7.8 W; ≤ 19.9 W (nominal load)
Efficiency (typ.)
91.7 %
Circuit protection
Internal fuse
3 x T 2.5 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 1.6 A;
Setting range: 1.6 ... 2.5 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
57 x 163 x 179; Height with connector
Mounting type
DIN-35 rail
Weight
1000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
94
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; DC OK contact
Item No.
PU
787-842
1
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Switch off the output and minimize power consumption
via stand-by input
Output monitoring via DC OK contact
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 1.1 A (340 VAC; 20 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 13 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
40 ADC (4 s); 30 ADC (16 s)
TopBoost
80 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 8.3 W; ≤ 34.1 W (nominal load)
Efficiency (typ.)
92.9 %
Circuit protection
Internal fuse
3 x T 2.5 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 2.5 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
77 x 171 x 179; Height with connector
Mounting type
DIN-35 rail
Weight
1300 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
95
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; DC OK contact
Item No.
PU
787-844
1
With lateral DIN-rail
support
787-844/000-002
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Switch off the output and minimize power consumption
via stand-by input
Output monitoring via DC OK contact
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 2 A (340 VAC; 40 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 13 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
40 A (24 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
60 ADC (4 s); 50 ADC (16 s)
TopBoost
100 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 7 W; ≤ 61.5 W (nominal load)
Efficiency (typ.)
93.6 %
Circuit protection
Internal fuse
3 x T 3.2 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 2.5 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +55 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®/ Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
128 x 171 x 205; Height with connector
Mounting type
DIN-35 rail
Weight
2500 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
96
2
www.wago.com
L1
DC+
DC+
DC -
DC -
L2
L3
S1
S3
S4
S2
RS-232
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
787 Series
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
Item No.
PU
787-850
1
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
LineMonitor for parameter setting and monitoring
RS-232 serial interface
Four signal outputs
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 0.6 A (340 VAC; 10 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive (adjustable via software/display)
Mains failure hold-up time
≥ 22 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Adjustable (constant current/fuse mode)
PowerBoost
20 ADC (4 s); 15 ADC (16 s)
TopBoost
70 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green)1 x Warning LED (yellow)1 x Error
LED (red)LCD1 x RS-232 interface
Operation status indicator
Green LED (DC OK); Yellow LED (warning); Red LED (error)
Communication
RS-232 serial interface
Efficiency/power losses
Power loss Pl
≤ 7.8 W; ≤ 19.9 W (nominal load)
Efficiency (typ.)
91.7 %
Circuit protection
Internal fuse
3 x T 2.5 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 1.6 A;
Setting range: 1.6 ... 2.5 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
57 x 163 x 179; Height with connector
Mounting type
DIN-35 rail
Weight
1000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
97
2
www.wago.com
L1
DC+
DC+
DC -
DC -
L2
L3
S1
S3
S4
S2
RS-232
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
787 Series
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
Item No.
PU
787-852
1
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
LineMonitor for parameter setting and monitoring
RS-232 serial interface
Four signal outputs
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 1.1 A (340 VAC; 20 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive (adjustable via software/display)
Mains failure hold-up time
≥ 13 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Adjustable (constant current/fuse mode)
PowerBoost
40 ADC (4 s); 30 ADC (16 s)
TopBoost
80 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Warning LED (yellow);1 x Error
LED (red); LCD; 1 x RS-232 interface
Operation status indicator
Green LED (DC OK); Yellow LED (warning); Red LED (error)
Communication
RS-232 serial interface
Efficiency/power losses
Power loss P
l
≤ 8.3 W; ≤ 34.1 W (nominal load)
Efficiency (typ.)
92.9 %
Circuit protection
Internal fuse
3 x T 2.5 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 2.5 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®/ Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
77 x 171 x 179; Height with connector
Mounting type
DIN-35 rail
Weight
1300 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
98
2
www.wago.com
L1
DC+
DC+
DC -
DC -
L2
L3
S1
S3
S4
S2
RS-232
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
787 Series
Switched-mode power supply; Pro; 3-phase;
24 VDC output voltage; 40 A output current;
TopBoost + PowerBoost; LineMonitor; DC OK signal
Item No.
PU
787-854
1
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per UL 60950-
1; PELV per EN 60204
LineMonitor for parameter setting and monitoring
RS-232 serial interface
Four signal outputs
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 2 A (340 VAC; 20 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive (adjustable via software/display)
Mains failure hold-up time
≥ 15 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22.8 ... 28.8 VDC (adjustable)
Nominal output current I
o nom
40 A (24 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Adjustable (constant current/fuse mode)
PowerBoost
60 ADC (4 s); 50 ADC (16 s)
TopBoost
100 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Warning LED (yellow);1 x Error
LED (red); LCD; 1 x RS-232 interface
Operation status indicator
Green LED (DC OK); Yellow LED (warning); Red LED (error)
Communication
RS-232 serial interface
Efficiency/power losses
Power loss P
l
≤ 7 W; ≤ 61.5 W (nominal load)
Efficiency (typ.)
93.6 %
Circuit protection
Internal fuse
3 x T 3.2 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 3.2 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +55 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®/ Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
128 x 171 x 205; Height with connector
Mounting type
DIN-35 rail
Weight
2300 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
99
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Switch off the output and minimize power consumption
via stand-by input
Output monitoring via DC OK contact
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; Pro; 3-phase; 48 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Switched-mode power supply; Pro; 3-phase;
48 VDC output voltage; 10 A output current;
TopBoost + PowerBoost; DC OK contact
Item No.
PU
787-845
1
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 1.1 A (340 VAC; 10 ADC)
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 12 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
39 ... 53 VDC (adjustable)
Nominal output current I
o nom
10 A (48 VDC)
Nominal output power
480 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
15 ADC (4 s); 12.5 ADC (16 s)
TopBoost
55 ADC (50 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 8.2 W (no load);
≤ 38 W (nominal load)
Efficiency (typ.)
93 %
Circuit protection
Internal fuse
3 x T 2.5 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 2.5 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)
Connection data
Connection technology
CAGE CLAMP®/ Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
77 x 171 x 179; Height with connector
Mounting type
DIN-35 rail
Weight
1883.3 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
100
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC O.K.
Stand-by
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Pro; 3-phase; 48 VDC output voltage; 20 A output current;
TopBoost + PowerBoost; DC OK contact
787 Series
Features:
Switched-mode power supply with PowerBoost and
TopBoost
Switch off the output and minimize power consumption
via stand-by input
Output monitoring via DC OK contact
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; Pro; 3-phase; 48 VDC
output voltage; 20 A output current; TopBoost +
PowerBoost; DC OK contact
Item No.
PU
787-847
1
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 340 ... 550 VAC; 480 ... 780 VDC
Nominal mains frequency range
50 ... 60 Hz; 0 Hz
Input current I
i
≤ 3 x 2 A (340 VAC; 20 ADC)
Inrush current
≤ 30 A (peak)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 15 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
48 VDC (SELV)
Output voltage range
39 ... 53 VDC (adjustable)
Nominal output current I
o nom
20 A (48 VDC)
Nominal output power
960 W
Residual ripple
≤ 70 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
TopBoost/PowerBoost/Constant current mode
PowerBoost
30 ADC (4 s); 25 ADC (16 s)
TopBoost
80 ADC (25 ms)
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Error LED (red); 1 x Stand-by
input; 1 x DC OK relay contact (changeover contact)
Operation status indicator
Green LED (DC OK); Red LED (error)
Efficiency/power losses
Power loss P
l
≤ 0.8 W (standby); ≤ 5.2 W (no load);
≤ 59.2 W (nominal load)
Efficiency (typ.)
94.4 %
Circuit protection
Internal fuse
3 x T 3.2 A / 440 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic:
B or C; Alternative: motor circuit breaker; Setpoint: 3.2 A;
Setting range: 2.5 ... 4 A
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-5 %/K (> 45 °C)
Connection data
Connection technology
CAGE CLAMP®/ Push-in CAGE CLAMP®
Input (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0.5 ... 10 mm² / 0.5 ... 10 mm² / 20 ... 8 AWG
Signaling (solid/fine-stranded/AWG)
0.08 ... 0.5 mm² / 0.08 ... 0.5 mm² / 28 ... 20 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
128 x 171 x 205; Height with connector
Mounting type
DIN-35 rail
Weight
3270 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3;
EN 61558-2-16; UL 60950; UL 508
101
2
www.wago.com
DC+
DC+
DC -
DC -
DC O.K.
L1
L2
L3
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Classic; 3-phase;
24 VDC output voltage; 10 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1640
1
Features:
Switched-mode power supply with TopBoost, enabling
secondary-side protection via circuit breakers
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
DC OK contact
Suitable for both parallel and series operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; Classic; 3-phase; 24 VDC output voltage; 10 A output current;
TopBoost; DC OK contact
787 Series
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 320 ... 575 VAC; 450 ... 800 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 0.73 A (400 VAC); ≤ 3 x 0.66 A (500 VAC)
Inrush current
≤ 30 A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 50 ms (500 VAC); ≥ 21 ms (400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 50 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 2.1 W; ≤ 27.9 W (400 VAC; nominal load)
Power loss (max.) P
l (max.)
28.3 W (500 VAC / 24 VDC; 10 A)
Efficiency (typ.)
90 %
Circuit protection
Internal fuse
No
Backup fusing (required)
Alternative: motor circuit breaker; An external DC fuse is
required for the DC input voltage.
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit ≤ 41 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-2.5 %/K (> 55 °C)
Connection data
Connection type
Input/Output/Signaling
Connection technology
CAGE CLAMP®
Solid/fine-stranded/AWG
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
55 x 127 x 171
Mounting type
DIN-35 rail
Weight
1000 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
102
2
www.wago.com
DC+
DC+
DC -
DC -
DC O.K.
L1
L2
L3
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Classic; 3-phase;
24 VDC output voltage; 20 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1642
1
Features:
Switched-mode power supply with TopBoost, enabling
secondary-side protection via circuit breakers
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
DC OK contact
Suitable for both parallel and series operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; Classic; 3-phase; 24 VDC output voltage; 20 A output current;
TopBoost; DC OK contact
787 Series
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 320 ... 575 VAC; 450 ... 800 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 1.21 A (400 VAC); ≤ 3 x 1.03 A (500 VAC)
Inrush current
≤ 30 A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 25 ms (500 VAC); ≥ 15 ms (400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 15 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 5.8 W; ≤ 42.8 W (400 VAC; nominal load)
Power loss (max.) P
l (max.)
47.6 W (500 VAC / 24 VDC; 20 A)
Efficiency (typ.)
92 %
Circuit protection
Internal fuse
No
Backup fusing (required)
Alternative: motor circuit breaker; An external DC fuse is
required for the DC input voltage.
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-2.5 %/K (> 55 °C)
Connection data
Connection technology
CAGE CLAMP®; Push-in CAGE CLAMP®
Input/ Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0,5 ... 10 mm² / 0,5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
80 x 127 x 180
Mounting type
DIN-35 rail
Weight
1623 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
103
2
www.wago.com
DC+
DC+
DC -
DC -
DC O.K.
L1
L2
L3
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Classic; 3-phase;
24 VDC output voltage; 40 A output current; TopBoost;
DC OK contact
Item No.
PU
787-1644
1
Switched-mode power supply; Classic; 3-phase; 24 VDC output voltage; 40 A output current;
TopBoost; DC OK contact
787 Series
Features:
Switched-mode power supply with TopBoost, enabling
secondary-side protection via circuit breakers
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
DC OK contact
Suitable for both parallel and series operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 320 ... 575 VAC; 450 ... 800 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 2.15 A (400 VAC); ≤ 3 x 1.82 A (500 VAC)
Inrush current
≤ 30 A (NTC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 25 ms (500 VAC); ≥ 15 ms (400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
23 ... 28.5 VDC (adjustable)
Nominal output current I
o nom
40 A (24 VDC)
Nominal output power
960 W
Residual ripple
≤ 30 mV (peak-to-peak)
Current limitation
1.1 x I
o nom
(typ.)
Overload behavior
Constant current
Signaling and communication
Signaling
1 x LED DC OK (green)
Operation status indicator
Green LED (U
o
)
Efficiency/power losses
Power loss P
l
≤ 4.2 W; ≤ 83.9 W (400 VAC; nominal load)
Power loss (max.) P
l (max.)
83.9 W (500 VAC / 24 VDC; 40 A)
Efficiency (typ.)
92 %
Circuit protection
Internal fuse
No
Backup fusing (required)
Alternative: motor circuit breaker; An external DC fuse is
required for the DC input voltage.
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit ≤ 40 VDC (in the event of a
fault)
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 500,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C (device starts at −40 °C, type-tested)
Ambient temperature (storage)
-25 ... +85 °C
Relative humidity
5 ... 96 % (no condensation permissible)
Derating
-2.5 %/K (> 55 °C)
Connection data
Connection technology
CAGE CLAMP®; Push-in CAGE CLAMP®
Input/ Signaling (solid/fine-stranded/AWG)
0.08 ... 2.5 mm² / 0.08 ... 2.5 mm² / 28 ... 12 AWG
Output (solid/fine-stranded/AWG)
0,5 ... 10 mm² / 0,5 ... 10 mm² / 20 ... 8 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
126 x 127 x 198
Mounting type
DIN-35 rail
Weight
2800 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 61010-1; EN 61010-2-201; EN 61204-3; UL 60950-1;
UL 508; DNV
104
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; ECO; 3-phase;
24 VDC output voltage; 6.25 A output current;
DC OK contact
Item No.
PU
787-738
1
Features:
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Fast and tool-free termination via lever-actuated PCB
terminal blocks
Bounce-free switching signal (DC OK) via optocoupler
Parallel operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Switched-mode power supply; ECO; 3-phase; 24 VDC output voltage; 6.25 A output current;
DC OK contact
787 Series
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 360 ... 575 VDC; 500 ... 650 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 0.6 A (400 VAC; 24 VDC / 6.25 A)
Inrush current
≤ 25 A
Power factor
≥ 0.5
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 17 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 28 VDC (adjustable)
Nominal output current I
o nom
6.25 A (24 VDC)
Nominal output power
150 W
Residual ripple
≤ 100 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.15 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Overload LED (red)
Operation status indicator
Green LED (U
o
); Red LED (overload)
Efficiency/power losses
Power loss P
l
≤ 18.5 W
Power loss (max.) P
l (max.)
20 W
Efficiency (typ.)
87 %
Circuit protection
Internal fuse
3 x T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker ≥ 6 A; Tripping characteristic: B or C;
Alternative: motor circuit breaker
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 250,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-2.5 %/K (> 50 °C; 400 VAC)
Connection data
Connection technology
CAGE CLAMP® / Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.5 ... 6 mm² / 0.5 ... 6 mm² / 20 ... 10 AWG
Signaling (solid/fine-stranded/AWG)
0.2 ... 1.5 mm² /0.2 ... 1.5 mm² / 24 ... 14 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
50 x 130 x 92
Mounting type
DIN-35 rail
Weight
844 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 62368-1; EN 61204-3 (Class A); UL 60950-1; UL 609
105
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; Eco; 3-phase;
24 VDC output voltage; 10 A output current;
DC OK contact
Item No.
PU
787-740
1
Switched-mode power supply; ECO; 3-phase; 24 VDC output voltage; 10 A output current;
DC OK contact
787 Series
Features:
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Fast and tool-free termination via lever-actuated PCB
terminal blocks
Bounce-free switching signal (DC OK) via optocoupler
Parallel operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 360 ... 575 VDC; 500 ... 650 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 1.2 A (400 VAC; 24 VDC / 10 A)
Inrush current
≤ 25 A
Power factor
≥ 0.5
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 17 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 28 VDC (adjustable)
Nominal output current I
o nom
10 A (24 VDC)
Nominal output power
240 W
Residual ripple
≤ 100 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.15 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Overload LED (red)
Operation status indicator
Green LED (U
o
); Red LED (overload)
Efficiency/power losses
Power loss P
l
≤ 32.5 W
Power loss (max.) P
l (max.)
36 W
Efficiency (typ.)
89 %
Circuit protection
Internal fuse
3 x T 2 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker ≥ 6 A; Tripping characteristic: B or C;
Alternative: motor circuit breaker
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 250,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-1.25 %/K (> 50 °C; 400 VAC)
Connection data
Connection technology
CAGE CLAMP® / Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.5 ... 6 mm² / 0.5 ... 6 mm² / 20 ... 10 AWG
Signaling (solid/fine-stranded/AWG)
0.2 ... 1.5 mm² /0.2 ... 1.5 mm² / 24 ... 14 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
65 x 130 x 130
Mounting type
DIN-35 rail
Weight
1265 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 62368-1; EN 61204-3 (Class A); UL 60950-1; UL 508
106
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Switched-mode power supply; ECO; 3-phase;
24 VDC output voltage; 20 A output current;
DC OK contact
Item No.
PU
787-742
1
Switched-mode power supply; ECO; 3-phase; 24 VDC output voltage; 20 A output current;
DC OK contact
787 Series
Features:
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Fast and tool-free termination via lever-actuated PCB
terminal blocks
Bounce-free switching signal (DC OK) via optocoupler
Parallel operation
Electrically isolated output voltage (SELV) per
UL 60950-1; PELV per EN 60204
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 500 VAC
Input voltage range
(2 / 3) x 360 ... 575 VDC; 500 ... 650 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 2 A (400 VAC; 24 VDC / 20 A)
Inrush current
≤ 30 A
Power factor
≥ 0.5
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 17 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 28 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 100 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.15 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Overload LED (red)
Operation status indicator
Green LED (U
o
); Red LED (overload)
Efficiency/power losses
Power loss P
l
≤ 50 W
Power loss (max.) P
l (max.)
55 W
Efficiency (typ.)
90 %
Circuit protection
Internal fuse
3 x T 5 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker ≥ 6 A; Tripping characteristic: B or C;
Alternative: motor circuit breaker
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/Yes
MTBF
> 250,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-25 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-2 %/K (> 50 °C; 400 VAC)
Connection data
Connection technology
CAGE CLAMP® / Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.5 ... 6 mm² / 0.5 ... 6 mm² / 20 ... 10 AWG
Signaling (solid/fine-stranded/AWG)
0.2 ... 1.5 mm² /0.2 ... 1.5 mm² / 24 ... 14 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
110 x 130 x 151
Mounting type
DIN-35 rail
Weight
1930 g
Standards and specifications
Conformity marking
CE
Standards/specifications
EN 62368-1; EN 61204-3 (Class A); UL 60950-1; UL 508
107
2
www.wago.com
L1
L2
L3
DC+
DC+
DC -
DC -
DC -
DC O.K.
WAGO Power Supplies
Section 2 | WAGO Power Supplies; 3-Phase
Power supply; ECO; 3-phase; 24 VDC output voltage;
20 A output current; DC OK contact
Item No.
PU
787-2742
1
Power supply; ECO; 3-phase; 24 VDC output voltage; 20 A output current; DC OK contact
787 Series
Features:
Economical power supply for standard applications
Natural convection cooling when horizontally mounted
Encapsulated for use in control cabinets
Fast and tool-free termination via lever-actuated termi
-
nal blocks with push-in connection technology
DC OK signal output
Parallel operation
Electrically isolated output voltage (SELV) per
EN 60950-1/UL 60950-1; PELV per EN 60204-1
Input
Phases
2 / 3
Nominal input voltage U
i nom
(2 / 3) x 400 ... 480 VDC
Input voltage range
(2 / 3) x 325 ... 575 VAC; 60 ... 700 VDC
Nominal mains frequency range
47 ... 63 Hz; 0 Hz
Input current I
i
≤ 3 x 1.2 A (400 VAC)
Inrush current
≤ 30 A (400 VAC)
Power factor
≥ 0.7 (400 VAC)
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 10 ms (3 x 400 VAC)
Output
Nominal output voltage U
o nom
24 VDC (SELV)
Output voltage range
22 ... 28 VDC (adjustable)
Nominal output current I
o nom
20 A (24 VDC)
Nominal output power
480 W
Residual ripple
≤ 150 mV (peak-to-peak)
Overload behavior
Constant power (in overload range: 1.05 ... 1.4 x I
o nom
);
Shutdown and automatic restart in the event of a short
circuit
Signaling and communication
Signaling
1 x LED DC OK (green); 1 x Overload LED (red); 1 x DC
OK signal output (PhotoMOS as make contact; can be
loaded with max. 31.2 V / 100 mA)
Operation status indicator
Green LED (U
o
); Red LED (overload)
Efficiency/power losses
Power loss P
l
≤ 2.15 W (400 VAC; no load);
≤ 42.5 W (400 VAC; nominal load)
Efficiency (typ.)
92 %
Circuit protection
Internal fuse
3 x T 3.15 A / 500 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
3 x circuit breaker ≥ 10 A; Tripping characteristic: B or C
Safety and protection/Environmental requirements
Isolation voltage (sec.-PE)
0.7 kVDC
Protection class/type
I / IP20; per EN 60529
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Short-circuit-protected/open-circuit-proof
Yes/Yes
Parallel/series operation
Yes/2 devices (max.)
MTBF
> 1,800,000 h (per IEC 61709)
Ambient temperature (operation at U
N
)
-20 ... +70 °C
Ambient temperature (storage)
-40 ... +85 °C
Relative humidity
10 ... 95 % (no condensation permissible)
Derating
-2 %/K (> 45 °C)
Resistance to shock and vibration
Shock: 15 g (per EN 60068-2-27);
Vibration: 1 g (per EN 60068-2-6)
Connection data
Connection technology
Push-in CAGE CLAMP®
Input/Output (solid/fine-stranded/AWG)
0.5 ... 6 mm² / 0.5 ... 6 mm² / 20 ... 10 AWG
Signaling (solid/fine-stranded/AWG)
0.2 ... 1.5 mm² / 0.2 ... 1.5 mm² / 24 ... 14 AWG
Physical data/Mechanical data/Material data
Width x Height x Depth from upper-edge of DIN-rail (mm)
80 x 130 x 170
Mounting type
DIN-35 rail
Weight
1710 g
Standards and specifications
Conformity marking
1; EAC
Standards/specifications
EN 61204-3; EN 62368-1; cURus 60950-1;
cURus 62368-1; cULus 508; CSA C22.2
108
2

您正在使用的浏览器版本过低,将不能正常浏览产品选型内容。

  • 收藏
服务热线

联系我们

954668/400-830-1766(工作日 9:00-18:00)

service@sekorm.com

投诉与建议

E-mail:claim@sekorm.com

商务合作

E-mail:contact@sekorm.com

收藏
收藏当前页面