Comparison of Advantages and Disadvantages Between 40G QSFP+SR4 Optical Module and QSFP+ AOC Active Optical Cable
Both 40G QSFP+SR4 optical transceivers and 40G QSFP+ AOC active optical cables are widely used in 40G data center for short-distance interconnection. Since both can realize short-distance interconnection, what is the difference between them and their advantages and disadvantages? Let's reveal the answer to everyone below.
1. The different power consumption of optical transceivers and active optical cables
The maximum power consumption of the 40G QSFP+SR4 optical transceivers is less than 3.5W, and the maximum power consumption of the 40G AOC active optical cables is less than 1.5W. Obviously, the power consumption of the 40G QSFP+SR4 optical transceivers is greater than that of the 40G AOC active optical cables.
2. The diagnostic monitoring functions of optical transceivers and active optical cables
40G QSFP+SR4 optical transceiver has DDM digital diagnostic monitoring functions, while 40G AOC active optical cable does not have DDM digital diagnostic monitoring function, so SR4 appears to be better than AOC in terms of receiving sensitivity.
3. The different use of optical transceivers and active optical cables
The 40G QSFP+ SR4 optical transceiver needs to be matched with a 12-core MPO multi-mode jumper to achieve interconnection, while the 40G AOC active optical cable comes with its own cable, which can be directly plugged into the device.
4. The different transmission distances of optical transceivers and active optical cables
The transmission distance of 40G QSFP+ SR4 optical transceivers is 100m/300m, while that of 40G AOC active optical cables is generally 70m.
5. The different insertion loss and return loss of optical transceivers and active optical cables
If the optical fiber is inserted into a 40G QSFP+ SR4 optical transceiver, repeated insertion and removal will cause different insertion loss and return loss, and 40G AOC is less affected by repeated insertion and removal during use. Therefore, the repeatability and interchangeability of 40G AOC active optical cable is stronger than that of 40G QSFP+ SR4.
6. The different eye diagrams used by optical transceivers and active optical cables
40G QSFP+ SR4 optical transceivers use optical eye diagrams to determine the quality of optical transceivers, while 40G AOC active optical cables use electrical eye diagrams to determine the quality of active optical cables.
7. The different connection test of optical transceivers and active optical cables
40G AOC active optical cables need to be tested in four quadrants. The four quadrants in a wide temperature range ensure that the MPO interface and optical cables of AOC will not melt at high temperatures. The 40G QSFP+ SR4 optical transceiver needs to be connected with an uncertain performance MPO jumper, so the integrated 40G AOC active optical cable ensures the performance of the product.
8. The different cost of optical transceivers and active optical cables
At present, the price of 40G AOC active optical cables is lower than 40G QSFP+ SR4 optical transceivers, and 40G QSFP+ SR4 optical transceiver also needs to be used with a 12-core MPO multi-mode jumper, so the cost of 40G QSFP+ SR4 optical transceivers is higher than that of 40G AOC active optical cables.
9. The different difficulty in installation and maintenance of optical transceivers and active optical cables
Using 40G AOC active optical cable can not only avoid the cleaning problem of optical transceivers, but also reduce the installation steps to help users save time.
Based on the above comparison, 40G QSFP+ AOC Active Optical Cable is more stable and reliable than 40G QSFP+ SR4 optical transceiver with easier installation and maintainence, and the interconnection cost is lower.
- |
- +1 赞 0
- 收藏
- 评论 0
本文由出山转载自T&S Blogs,原文标题为:Comparison of Advantages and Disadvantages Between 40G QSFP+SR4 Optical Module and QSFP+ AOC Active Optical Cable,本站所有转载文章系出于传递更多信息之目的,且明确注明来源,不希望被转载的媒体或个人可与我们联系,我们将立即进行删除处理。
相关推荐
What is an Optical Module?
The function of the optical module is photoelectric conversion. The transmitter converts the electrical signal into the optical signal, and then the receiver converts the optical signal into the electrical signal after transmission through the optical fiber.
What is the Difference Between AOC and Optical Transceiver?
AOC active optical cable is an optical fiber with a module attached to each end, which is equivalent to a cable and a module.AOC active optical cable is also widely used by many customers because its cost is cheaper than that of two separate modules plus one optical fiber.
Knowledge Sharing about SFP+ AOC
T&S can provide AOC and DAC cables required for the construction of large-scale data centers in 10G/40G/100G applications. The transmission media of AOC and DAC cables are different. For AOC, the signal transmits through light; for DAC, the signal transmits through electricity.
太辰光(T&S)光纤连接器选型指南
目录- 公司简介 Company profile 陶瓷插芯 Ceramic Ferrule 光纤连接器 Fiber Optic Cable Assembly 光纤元器件 Fiber Optic Components 波分复用器 WDM FBT光纤耦合器 FBT Coupler PLC分路器 PLC Splitter 光纤光栅 Fiber Bragg Grating 光纤模块、有源光缆及有源电缆 Fiber Optic Transceivers,AOC&DAC
型号- FOT-SC/APC,CG-XX/G652D/1.5M,D12F-SC/UPC/SM/∅0.9/L/L1M,SMC-P-1X2-163/15-10/90-FC/APC-1-G652D-∅3X60,FEN-SC-S4,FEN-SC-S5,MC-FC/APC-FC/UPC/SM/∅3/L,FEN-SC-S1,PM-FC/UPC(N)-FC/UPC(N)/1550/∅2/L-SA,FEN-SC-S2,FEN-SC-S3,ATIL-FC/APC/SM/05/NP/L,MPO/APC/12F-FC/UPC/SM/∅0.9-L/L1-RJ,PLC-1X8-A-09/L1-LC/UPC-09/L2-LC/UPC
太辰光(T&S)光纤通信产品选型指南
描述- 深圳太辰光通信股份有限公司成立于2000年,于2016年12月在深圳证券交易所创业板上市,证券代码300570,公司的主营业务为各种光通信器件及其集成功能模块的研发、生产和销售。光通信器件主要包括高密度光纤连接器、常规光纤连接器件、PLC光分路器、波分复用器等无源光器件、光模块、有源光缆等有源光器件以及陶瓷插芯、MT插芯,平面光波导晶圆和芯片等基础元器件。
型号- TSSLS-NCNEE3C,400G QSFP-DD TO 4X100G QSFP56 AOC,200G QSFP56 SR4,400G QSFP-DD TO 8X50G SFP56 DAC,TSSLS-NXXCE3T,TSQM4-NAAJB1C,TSQS-PC40G-XXM,TSD4Q-85M-XXXC,TS-RD1,TS-RD1-1U,TSD8S-85M-XXXC,TSQSQ-85G-XXXC,TSQ45-85G-XXXC,TSQM4-NAAJB1T,TS-FD2,TSSLS-NXXCE3C,TS-FD1-1U,TS-FD1,40G QSFP+TO 4X10G SFP+DAC,PD2-6M,TSSLS-NCNEH8C,40G QSFP+ TO 4X10G SFP+ AOC,TSQS-PC56G-XXM,FEN-LH-SMA,TS-FD2 SERIES,56G QSFP+DAC,40G QSFP+ ER4,TSQD-PC4HG-XXM,200G QSFP56 AOC,10G SFP+ ZR,FEN-LH-LC,100G QSFP28 PSM4,TSSLS-CXXEE3C,25G SFP28 SR,TSSLS-NAACBIT,TSSLS-NAAEAIT,TSQDQ-4PC1HG-XXM,100G QSFP28 AOC,TSSLS-NAACB1C,TSSLS-NAAEA1C,FEN-LH-SDL,10G SFP+ DWDM,MD2-1M24L,TSQL4-E11GH7C,TSQSS-PC2HG-XXM,TSQL4-F22JH4C,FES-LC-PA,25G SFP28 DAC,25G SFP28 CWDM,400G QSFP-DD DAC,400G QSFP-DD DR4,TSSLS-NCNCE3C,400G QSFP-DD TO 2X200G QSFP56 DAC,MD1-3M24L,TSSP-PC25G-XXM,TSD2Q-85L-XXXC,200G QSFP56 TO 4X50G SFP56 AOC,56G QSFP+ AOC,TSSP-PC56G-XXM,TSQS-PC2HG-XXM,100G QSFP28 SR4,10G SFP+ LR,TSQM4-NCNJC3C,TSQSS-PC1HG-XXM,TS-RD1 SERIES,TSSSS-85H-XXXC,TSQDQ-2PC2HG-XXM,50G SFP56 AOC,40G QSFP+ DAC,TS-FD1 SERIES,TSQSQ-85H-XXXC,TSQM4-NAALAIC,FEN-SC-FUNNEL-1,PD2-24L,FEN-SC-FUNNEL-2,TSQM4-NAAGB1C,TSQM4-NAAGBIT,TSSSS-85E-XXXC,40G QSFP+ LR4,TSSLS-CXXCE3C,FES-SC-PA,TSQS-PC1HG-XXM,200G QSFP-DD TO 2X100G QSFP28 AOC,100G QSFP28 TO 2X50G QSFP28 AOC,TSSLS-DXXEE4C,10G SFP+ DAC,25G SFP28 BIDI,TSSLS-NCNEE3T,100G QSFP28 LR4,TSQ4S-85L-XXXC,TSQSQ-85L-XXXC,100G QSFP28 DAC,TSDM4-NCNMC3C,25G SFP28 ER,10G SFP+ AOC,10G SFP+ BIDI,400G QSFP-DD TO 8X50G SFP56 AOC,800G QSFP-DD AOC,TSQM4-NCNGC3C,TSDR8-NAAMATC,TS-FD2-2U,10G SFP+ CWDM,10G SFP+SR,FEN-LC-2,25G SFP28 DWDM,TSSSS-85C-XXXC,TSDSD-85N-XXXC,100G QSFP28 TO 4X25G SFP28 AOC,TSQDS-8PC50G-XXM,800G QSFP-DD SR8,10G SFP+ ER,200G QSFP56 DAC,100G SFP-DD AOC,TSSLS-DXXCK8C,TSQ2Q-85J-XXXC,TSSLS-NCNCE3T,TSQSQ-PC2HG-XXM,TSD2Q-85M-XXXC,FEN-LH-SC,TSSLS-NXXEE3T,200G QSFP56 FR4,40G QSFP+ AOC,50G SFP56 DAC,100G QSFP28 TO 4X25G SFP28 DAC,100G QSFP28 ER4,FEN-SC-1,TSDSD-85M-XXXC,400G QSFP-DD FR4,TSDL4-E11MD3C,100G QSFP28 CWDM4,TSSLS-NXXEE3C,25G SFP28 LR,40G QSFP+PSM4,TSQL4-F22JE3C,400G QSFP-DD TO 2X200G QSFP56 AOC,TSTST-85K-XXXC,400G QSFP-DD AOC,TSQSQ-85J-XXXC,TSQ4S-85J-XXXC,TSD85-85L-XXXC,TSQL4-E11JE3C,TSDR8-NAANA1C,TSSLS-NCNCKBC,200G QSFP56 TO 4X50G SFP56 DAC,TSQL4-E11LD3C,400G QSFP-DD TO 4X100G QSFP56 DAC,200G QSFP-DD TO 8X25G SFP28 AOC,TSSLS-NCNCH4C,MD1-2M6M,200G QSFP56 TO 2X100G QSFP56 DAC,25G SFP28 AOC,PD1-24L,TSQL4-E11GE3C,400G QSFP-DD SR8,40G QSFP+SR4,TSQSS-PC40G-XXM,TSSLS-DXXCH4C,TSSP-PC192-XXM
Type Selection and Application of Fiber Transceiver
Although optical modules are a trend to replace fiber transceivers, there is still a relatively large user base for fiber transceivers. For example, fiber transceivers are still commonly used transmission products in monitoring systems.
电子商城
登录 | 立即注册
提交评论