Laird Thermal Systems‘ Testing Liquid Cooling Systems Can Be Tailored According to Customer Specifications and Applicable Industry Standards

2024-09-30 Laird Thermal Systems Official Website
Liquid cooling systems,Chiller Platform,Liquid Heat Exchangers,Liquid Chillers Liquid cooling systems,Chiller Platform,Liquid Heat Exchangers,Liquid Chillers Liquid cooling systems,Chiller Platform,Liquid Heat Exchangers,Liquid Chillers Liquid cooling systems,Chiller Platform,Liquid Heat Exchangers,Liquid Chillers

Laird Thermal Systems has conducted several decades of validation testing on various combinations of thermal components to optimize cooling power and efficiency at various heat loads while minimizing noise. Their reliability and functional testing can be tailored according to customer specifications and applicable industry standards.


·Reliability testing – ensures mechanical integrity of the liquid cooling system

·Functional testing – ensures that the system meets expected performance

·Compliance - verifies that the liquid cooling unit meets applicable industry standards

·Quality Control – end of line test to ensure high-quality products
 

Mechanical Testing


G-force Testing


OEMs within specific application of the medical sector are required to perform g-force testing on all components to ensure operational safety of the equipment. With inhouse gantry testing equipment, Laird Thermal Systems can deliver Liquid cooling systems tested to withstand high g-forces. This allows them to test and evaluate components as well as systems from the designing to manufacturing process, saving time and cost for OEM customers. They also test mechanical strength of the product to make sure that mountings or fasteners do not fail due to high g-forces.
 

Laird Thermal Systems Gantry Testing Capability

·Capable of testing up to 100 g-forces

·Ability to test single components to complete systems mounted in various orientations

Depending on the requirements, these tests can run for many months. During the test we will log information such as temperature, flow and pressure at different g-forces.


Performance Testing


Cooling Capacity


Their test engineers will run multiple cooling capacity tests to make sure the liquid cooling system delivers expected performance at various heat loads. The result will be presented in a performance graph showing cooling capacity (Watts) versus temperature differential Delta T (∆) at a given ambient temperature. All our data sheet performance graphs have a tolerance of 10%.
 

How is the test performed?

·The liquid cooling system is placed in a climatic chamber at various environmental temperatures.

·A liquid circuit with inline heaters is used to generate heat load.

·For Liquid Heat Exchangers, temperature differential (ΔT) for performance graph is calculated by subtracting ambient temperature and temperature of liquid out to customer application.

·For Liquid Chillers, performance is graphed as heat load at a given setpoint at various ambient conditions.


Control Temperature


This test is typically only conducted for chiller units, because temperature control is a critical aspect of the system’s performance.
 

How is the test performed?

·The chiller will run at normal operating conditions in a climatic chamber at the temperature intended for use.

·We will measure temperature stability to ensure it meets application requirements. Our Nextreme Chiller Platform achieves a temperature stability of +/-0.1°C which is sufficient for most applications.

·During design validation, testing is also conducted to optimize the systems response to both positive and negative changes in heat load and setpoint.


Airflow & Liquid/Air Pressure Drop


Understanding air flow and temperature distribution is the key to developing the optimum thermal management system. Laird Thermal Systems engineers utilize wind tunnels to program the desired air flow in order to optimize cooling performance while minimizing noise and size of heat exchangers.
 

Laird Thermal Systems wind tunnel capabilities

·Volume air flow measurement

·Air speed measurement

·Capable of creating variable laminar homogenous air flow

·Controllable heat injection

·Variable pump speed

·Liquid/Air pressure drop measurements

·Liquid/Air flow measurements

·Liquid/Air temperature measurements


Noise


No matter the industry, manufacturers of any equipment are always seeking ways to reduce noise. In thermal systems, noise is a result of vibrations generated by components such as pumps, fans and air ducts. Because it is more complicated to reduce noise when a product is already built, Laird Thermal Systems measures and evaluates noise throughout the entire process, from the design stage and selecting components to product sign-off.
 

How is the test performed?

·Laird Thermal Systems utilizes acoustic analyzers with Class 1 microphone in accordance with IEC 61672 standard, enabling reliable long-term and frequency measurements.

·We perform noise measurements in accordance with ISO 12001:1996, accuracy grade 3 (survey grade) to achieve comparable results.

·If customers require standards beyond our inhouse capabilities, for example, EN 3746 or EN61010-1, testing can be performed in accredited labs with our external partner.


Compliance


ROHS, REACH, TSCA. CA PROP 65


Laird Thermal Systems is committed to providing products that meet regulatory requirements and are environmentally safe.


Their liquid cooling systems comply with

·RoHS - the Restriction of Hazardous Substances

·REACH - the Registration, Evaluation, Authorisation and Restriction of Chemicals (Europe)

·TSCA - Toxic Substances Control Act (US)

·CA PROP 65 - Safe Drinking Water and Toxic Enforcement Act (US, California)

 

Read more about our environmental and safety work or request product compliance certification here.


EMC/EMI


Electromagnetic Compatibility (EMC) and Electromagnetic Interference (EMI) testing are critical steps to ensure product safety and performance.

While EMI can be defined as the phenomenon of electromagnetic disturbance, EMC is an equipment characteristic. EMC testing will determine the product’s ability to properly function independent of environments with electromagnetic interference as well as ensuring that surrounding equipment will not be affected.
 

How is the test performed?

·Laird Thermal Systems engineers perform this testing in accredited labs at our external partner.

·During testing the unit will operate at intended operating conditions in similar environmental condition as specified in applicable standards or according to customer specifications.

·Laird Thermal Systems EMC testing complies with:
- Residential, commercial and light -industrial environments immunity standard EN 61000-6-1:2007
- Residential, commercial and light -industrial environments emission standard EN 61000-6-3:2007 and EN 61000-6-3/A1:2011
- Industrial environment immunity standard EN 61000-6-2:2005
- Industrial environment emissions standard EN 61000-6-4:2007 and EN 61000-6-4/A1:2011
 

Liquid cooling systems will only pass the test if they comply with the emissions and immunity requirements of the applicable standard or, customer specified requirement.


UL-Testing


Underwriter Laboratories (UL) is a leading global certification company known for conducting some of the most rigorous and extensive safety testing programs on the market. Not only do these tests identify and eliminate immediate danger such as electrical shock, hot surfaces, sharp edges, and moving parts, but they also ensure items such as complying with maximum current draw in intended installation regions. Due to the complexity of liquid cooling systems, most of the UL testing program is often required according to certain standards.
 

How is the test performed?

·Laird Thermal Systems will provide UL with a testing unit and all relevant documentation (component datasheets, system diagrams, risk analysis, etc.) in good time before product release.

·UL will test the unit at both normal and above normal operating conditions to make sure it conforms with regional standards.

·Test results will be fully transparent and UL will provide recommendations on how to improve mechanical and electrical design to meet product requirements.

·UL certification will be successful once the product passes all testing criterion. Final test reports are available upon request.


End-of-Line Testing


Visual Inspection


The liquid cooling system will go through a visual inspection where following criteria will be checked:

·Dimensions are accurate 

·No scratches or defective paint

·Corners are chamfered, without sharp edges

·Connection points are tightened

·No missing or loose screws

·System is free of liquid from testing

·Inlet and outlet fittings are protected for shipment

·Product is appropriately labeled  


Hi-Pot Test


Products will go through a Hi-Pot or dielectric withstand test to ensure that insulation of the liquid cooling system is sufficient to prevent current leakage at normal operating voltage conditions. This is a required product test by UL.


Ground Leakage


This is a critical safety test to verify that the unit does not leak excessive current when contacted by the user, potentially resulting in severe injury. This is a required product test by UL.


Helium Vacuum Test


Coolant leakage has a significant impact on product performance and is one of the biggest challenges when designing a liquid cooling system. We are proud to offer the capability to perform helium vacuum testing on liquid-based cooling units during production and validation testing to ensure tight and reliable systems.
 

How is the test performed?

·The Liquid Cooling system is vacuumed in the chamber before testing to ensure maximum accuracy.

·The system is filled up with nitrogen to verify that there are no major leaks.

·If no leaks are detected, the system will be vacuumed again and pressurized with helium. Because helium gas has the smallest molecule size it offers the best chances to detect the tiniest pinhole leaks.

·A helium detector will identify and measure the concentration of helium in the testing chamber to make sure leakage from the unit has not exceeded an acceptable level.

·A leak detector helps us locate the leakages in order for us to rework the unit and ensure the system is properly sealed.


Performance

Liquid cooling systems will undergo extensive performance testing to verify that they meet expected requirements. Together with the customer (internal or external), Laird Thermal Systems engineering and operations team will determine the best methods to verify performance of each system. These can be for example coolant flow, temperature stability and cooling capacity.


授权代理商:世强先进(深圳)科技股份有限公司
技术资料,数据手册,3D模型库,原理图,PCB封装文件,选型指南来源平台:世强硬创平台www.sekorm.com
现货商城,价格查询,交期查询,订货,现货采购,在线购买,样品申请渠道:世强硬创平台电子商城www.sekorm.com/supply/
概念,方案,设计,选型,BOM优化,FAE技术支持,样品,加工定制,测试,量产供应服务提供:世强硬创平台www.sekorm.com
集成电路,电子元件,电子材料,电气自动化,电机,仪器全品类供应:世强硬创平台www.sekorm.com
  • +1 赞 0
  • 收藏
  • 评论 0

本文由samsara转载自Laird Thermal Systems Official Website,原文标题为:Testing Liquid Cooling Systems,本站所有转载文章系出于传递更多信息之目的,且明确注明来源,不希望被转载的媒体或个人可与我们联系,我们将立即进行删除处理。

相关研发服务和供应服务

评论

   |   

提交评论

全部评论(0

暂无评论

相关推荐

莱尔德热系统将在2024 CIOE中国光博会上展出下一代主动制冷技术

莱尔德热系统(Laird Thermal Systems)将于9月11日至13日在深圳国际会展中心参加2024年中国国际光电博览会(简称:CIOE中国光博会),展位位于12号馆信息通信展的12A69。

2024-09-10 -  原厂动态 代理服务 技术支持 批量订货

莱尔德热系统提供两种类型的液体冷却解决方案,冷却能力100W-25KW,使用寿命超过20年

莱尔德热系统(Laird Thermal Systems)液体冷却解决方案具有从100瓦到25K瓦以及更高的冷却能力,设计用于在高于、低于或等于环境温度时最大限度地保持温度稳定性,使用寿命能超过20年。

2022-06-04 -  原厂动态 代理服务 技术支持 批量订货

Laird Thermal Systems to Showcase Next Generation Active Cooling Technologies at CIOE 2024 - China International Optoelectronic Exhibition

Laird Thermal Systems will be exhibiting its newest active thermal products that solve thermal problems in applications including optical transceivers, imaging sensors, lasers and autonomous systems at the 2024 China International Optoelectronic Exhibition from September 11th through the 13th.

2024-08-23 -  原厂动态 代理服务 技术支持 批量订货

Laird Thermal Systems(莱尔德热系统)液体冷却系统产品选型指南

目录- Introduction    Benefits & Applications of Liquid Cooling Systems    Nextreme™ Recirculating Chillers    Liquid Heat Exchangers    Custom Liquid Cooling Systems    Featured Application: Medical Imaging   

型号- 1510.00,WL1500,385901-001,VRC2400,VRC4500,NRC5000,WL3004,387008451,1550.00,LA5000,WL1000,385911-015,1520.00,387009925,OW4002,385910-043,387010178,387010179,NRC2400,1505.00,38701 0181,1264.00,1155.00,1104.00,VRC1200,WW5001,387002779,NRC400,WW3001,1515.00,WL500,WL2000,387005774,387005598,OL4503,385912-029,NRC1200,385910-015

050422  - LAIRD THERMAL SYSTEMS  - 选型指南 代理服务 技术支持 批量订货

What are the benefits of using liquid instead of air cooling systems?

Liquid heat exchangers can reduce the thermal resistance of conventional heat sink fan dissipation mechanisms by a factor of 10 or more, which makes it much more efficient. This is due to the poor thermal properties of air versus coolants such as water. Liquid cooling systems have a more rapid cool down time, which means less time to reach the desired temperature. While conventional air cooling systems push air all around the system, and can potentially add heat from surrounding hot electronics, liquid cooling systems are equipped with a heat exchanger that routes heat away through a liquid circuit. Air-cooling systems in the higher capacity range often require larger fans, which can increase noise as well as the size of the system.

2024-10-30 -  技术问答

【产品】莱尔德热系统推出新一代制冷机Nextreme NRC400,温度控制精准,性能系数更高

莱尔德热系统(Laird Thermal Systems)推出的Nextreme NRC400是下一代台式循环冷却器,它利用固态热电技术为分析和工业设备提供精准的温度控制。

2022-05-18 -  产品 代理服务 技术支持 批量订货

WL1500 WL系列液体冷却系统

描述- WL1500是一款可靠的液体到空气热交换器,通过高效循环冷却液来移除大量热量。它采用高压泵确保最大流量,并通过辐射式换热器和风扇将热量散发到环境中。该设备包含空气和水过滤器以保持最佳性能,并提供手动调节功能控制液体电路的压力和流量。

型号- WL1500,WL SERIES

2019/2/13  - LAIRD THERMAL SYSTEMS  - 数据手册 代理服务 技术支持 批量订货

Does LTS offer standalone cooling systems?

Yes, Laird Thermal Systems offers self-contained Liquid Cooling Systems. liquid cooling systems (LCS) that recirculate a coolant to a preprogrammed temperature setpoint.

2024-10-30 -  技术问答

针对投影激光器的热电制冷器:莱尔德热系统UltraTEC™ UTX系列,运行噪音低,能耗降低多达50%

热电制冷器可提供局部点冷却,以保证卓越的温度稳定性,从而保持激光器和光电子器件的峰值性能。由于其固态运行,像Laird Thermal Systems UltraTEC UTX系列这样的热电冷却器可实现低维护和长寿命运行。通过在先进材料科学方面的突破,与标准热电冷却器相比,该产品系列能够提供更高的性能和更高的性能系数。

2024-10-25 -  应用方案 代理服务 技术支持 批量订货

What is the Thermal Wizard?

The Thermal Wizard is a product search and selection tool that helps engineers find the optimal thermal management solution for thermoelectric coolers, thermoelectric cooler assemblies and liquid cooling systems.

2024-10-30 -  技术问答

Common Coolant Types and Their Uses in Liquid Cooling Systems

This paper mainly introduces the common coolant types of Laird thermal system and its application in liquid cooling system, and analyzes the advantages and disadvantages of specific applications

2024-09-19 -  技术探讨 代理服务 技术支持 批量订货

莱尔德热系统Nextreme™ Value系列上市新机型,为医疗、工业和分析设备制造商提供经济解决方案

Laird Thermal Systems的Nextreme™ Value 冷水机系列又上市了1200瓦和4500瓦两种新机型,VRC1200和VRC4500能够针对特定应用提供所需的配置,是医疗、工业和分析仪器等行业原始设备制造商的理想制冷解决方案。

2023-05-16 -  新产品 代理服务 技术支持 批量订货

How do I determine the best thermal solution for my application?

Laird Thermal Systems has developed the Thermal Wizard — a quick and easy selection tool helping customers determine the optimum cooling solution. To begin the selection process, users can input two application performance requirements; the required cooling power (Qc) and the desired temperature change (ΔT). If you know these specifications the Thermal Wizard product search will show thermoelectric coolers, thermoelectric cooler assemblies or liquid cooling systems that meet your application demands.

2024-10-30 -  技术问答

WL500 WL系列液冷系统

描述- 该资料介绍了WL500液体冷却系统,这是一种循环液态空气热交换器,通过高效的热量转移能力,从液体回路中移除大量热量。它具有高泵送能力和紧凑的设计,适用于医疗诊断与治疗、工业仪器和半导体制造等领域。

型号- WL SERIES,WL500

2019/2/13  - LAIRD THERMAL SYSTEMS  - 数据手册 代理服务 技术支持 批量订货
展开更多

电子商城

查看更多

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥189.9800

现货: 100

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥265.3100

现货: 39

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥229.2800

现货: 34

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥478.2100

现货: 33

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥368.4800

现货: 32

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥281.6900

现货: 25

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥301.3400

现货: 21

品牌:Laird Thermal Systems

品类:Thermoelectric Coolers

价格:¥386.5000

现货: 20

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥378.3100

现货: 20

品牌:Laird Thermal Systems

品类:半导体制冷片(TEC)

价格:¥286.6000

现货: 20

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

品牌:

品类:

价格:

现货:

现货市场

查看更多

暂无此商品

海量正品紧缺物料,超低价格,限量库存搜索料号

服务

查看更多

散热方案设计

使用FloTHERM和Smart CFD软件,提供前期热仿真模拟、结构设计调整建议、中期样品测试和后期生产供应的一站式服务,热仿真技术团队专业指导。

实验室地址: 深圳 提交需求>

ATP半导体冷板制冷器定制

可定制ATP TE Cooler的冷却功率:40~200W;运行电压:12/24/48V(DC);控温精度:≤±0.1℃; 尺寸:冷面:20*20~500*300;热面:60*60~540*400 (长*宽;单位mm)。

最小起订量: 1 提交需求>

查看更多

授权代理品牌:接插件及结构件

查看更多

授权代理品牌:部件、组件及配件

查看更多

授权代理品牌:电源及模块

查看更多

授权代理品牌:电子材料

查看更多

授权代理品牌:仪器仪表及测试配组件

查看更多

授权代理品牌:电工工具及材料

查看更多

授权代理品牌:机械电子元件

查看更多

授权代理品牌:加工与定制

世强和原厂的技术专家将在一个工作日内解答,帮助您快速完成研发及采购。
我要提问

954668/400-830-1766(工作日 9:00-18:00)

service@sekorm.com

研发客服
商务客服
服务热线

联系我们

954668/400-830-1766(工作日 9:00-18:00)

service@sekorm.com

投诉与建议

E-mail:claim@sekorm.com

商务合作

E-mail:contact@sekorm.com

收藏
收藏当前页面